High-Voltage Connections
The unit must have a separate electrical service with a field-supplied,
waterproof disconnect switch mounted at, or within sight from the unit.
Refer to the unit rating plate, NEC and local codes for maximum
fuse/circuit breaker size and minimum circuit amps (ampacity) for wire
sizing.
The field-supplied disconnect may be mounted on the unit over the
high-voltage inlet hole when the standard power and low-voltage entry
points are used. See Fig. 2 and Fig. 3 for acceptable location.
See unit wiring label (Fig. 14 - Fig. 19) and Fig. 10 for reference when
making high voltage connections. Proceed as follows to complete the
high-voltage connections to the unit.
Single phase units:
1. Run the high-voltage (L1, L2) and ground lead into the control box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the
contactor.
4. Connect field L1 to black wire from connection 11 of the
compressor contactor.
5. Connect field wire L2 to yellow wire from connection 23 of the
compressor contactor.
A13176
Fig. 10 – High- and Control-Voltage Connections
Three-phase units:
1. Run the high-voltage (L1, L2, L3) and ground lead into the control
box.
2. Connect ground lead to chassis ground connection.
3. Locate the black and yellow wires connected to the line side of the
contactor.
4. Connect field L1 to black wire from connection 11 of the
compressor contactor.
5. Connect field wire L3 to yellow wire from connection 13 of the
compressor contactor.
6. Connect field wire L2 to blue wire from compressor.
Special Procedures for 208-V Operation
Control Voltage Connections
NOTE: Do not use any type of power-stealing thermostat. Unit control
problems may result.
Use no. 18 American Wire Gage (AWG) color-coded, insulated (35°C
minimum) wires to make the control voltage connections between the
thermostat and the unit. If the thermostat is located more than 100 ft
(30.5 m) from the unit (as measured along the control voltage wires), use
no. 16 AWG color-coded, insulated (35° C minimum) wires.
Standard Connection
Locate the nine low voltage thermostat leads (eight for 460 VAC
models) in 24 volt splice box. See Fig. 10 for connection diagram. Run
the low-voltage leads from the thermostat, through the control wiring
inlet hole grommet (Fig. 2 and Fig. 3), and into the low-voltage splice
box. Provide a drip loop before running wires through panel. Secure and
strain relief all wires so that they do not interfere with operation of unit.
CAUTION
!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in damage to the unit being
installed.
1. Make all electrical connections in accordance with NFPA 70
(NEC) (latest edition) and local electrical codes governing such
wiring. In Canada, all electrical connections must be in
accordance with CSA standard C22.1 Canadian Electrical Code
Part 1 and applicable local codes. Refer to unit wiring diagram.
2. Use only copper conductor for connections between
field-supplied electrical disconnect switch and unit. DO NOT
USE ALUMINUM WIRE.
3. Be sure that high-voltage power to unit is within operating
voltage range indicated on unit rating plate. On 3-phase units,
ensure phases are balanced within 2 percent. Consult local
power company for correction of improper voltage and/or phase
imbalance.
4. Do not damage internal components when drilling through any
panel to mount electrical hardware, conduit, etc.
5. Route field power supply(s) away from areas that could be
damaged by lawn and garden equipment or other accidental
damage.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing system, always turn off main power to
system and install lockout tag. With disconnect switch open, move
black wire from transformer (3/16 in.)(4.8 mm) terminal marked 230 to
terminal marked 208. This retaps transformer to primary voltage of 208
vac.