50VR-K: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
outdoor temperature is below 40°F (4°C) (unless accessory low-ambient
kit is installed).
IMPORTANT: Three-phase, scroll compressors are direction oriented.
Unit must be checked to ensure proper compressor 3-phase power lead
orientation. If not corrected within 5 minutes, the internal protector will
shut off  the  compressor. The  3-phase  power  leads  to  the  unit  must  be
reversed  to  correct  rotation.  When  turning  backwards,  the  difference
between compressor suction and discharge pressures may be near zero. 
Checking and Adjusting Refrigerant Charge
The refrigerant system is fully charged with R-410A  refrigerant and is
tested and factory sealed.
NOTE:  Adjustment of the refrigerant charge is not required unless the
unit is suspected of not having the proper R-410A charge. 
A subcooling charging chart is attached to the inside of the compressor
access panel. The chart includes the required liquid line temperature at
given discharge line pressures and outdoor ambient temperatures.
An accurate thermocouple- or thermistor-type thermometer, and a gauge
manifold are  required  when using  the  subcooling  charging  method  for
evaluating  the  unit  charge.  Do  not  use  mercury  or  small  dial-type
thermometers  because  they  are  not  adequate  for  this  type  of
measurement.
NOTE: Allow system to operate on high stage cooling for a minimum of
15 minutes before checking or adjusting refrigerant charge.
IMPORTANT:  When  evaluating  the  refrigerant  charge,  an  indicated
adjustment to the specified factory charge must always be very minimal.
If  a  substantial  adjustment  is  indicated,  an  abnormal  condition  exists
somewhere  in  the  cooling  system,  such  as  insufficient  airflow  across
either coil or both coils.
1. Remove caps from low- and high-pressure service fittings.
2. Using  hoses  with  valve  core  depressors,  attach  low-  and
high-pressure  gauge  hoses  to  low-  and  high-pressure  service
fittings, respectively.
3. Start unit and let run until system pressures stabilize.
4. Measure and record the following:
a. Outdoor ambient-air temperature (°F [°C] db).
b. Liquid line temperature (°F [°C]) at TXV.
c. Discharge (high-side) pressure (psig). 
d. Suction (low-side) pressure (psig) (for reference only).
5. Using Cooling Charging Charts (See Fig. 20) compare outdoor-air
temperature (°F [°C] db) with the discharge line pressure (psig) to
determine  desired  system  operating  liquid  line  temperature  (See
Fig. 20).
6. Compare  actual  liquid  line  temperature  with  desired  liquid  line
temperature. Using a tolerance of ±2°F (±1.1°C), add refrigerant if
actual  temperature  is  more  than  2°F  (1.1°C)  higher  than  proper
liquid line temperature, or remove refrigerant if actual temperature
is  more  than  2°F  (1.1°C)  lower  than  required  liquid  line
temperature.
NOTE:  If the problem causing the inaccurate readings is a refrigerant
leak, refer to Check for Refrigerant Leaks section.
Indoor Airflow and Airflow Adjustments
NOTE: Be sure that all supply-air and return-air grilles  are open,  free
from obstructions, and adjusted properly.
This unit has independent fan speeds for low stage cooling and high 
stage cooling. In addition, 208/230 VAC models have the 
field-selectable capability to run enhanced dehumidification 
(’DEHUM’) speeds on low stage and high stage cooling (as low as 320 
CFM per ton). Coupled with the improved dehumidification associated 
with low stage cooling, the DHUM speed allows for a complete 
dehumidification solution independent of cooling stage. 208/230 VAC 
models also have independent fan speeds for low stage gas heating and 
high stage gas heating as well as a dedicated continuous fan speed. 460 
VAC models offer a single gas heating speed and dedicated continuous 
fan speed. Table 7 and Table 8 show the operation modes and the 
associated fan speeds with each mode:
Table 3 shows  the operation modes and the associated  fan speeds with
each mode for all models:
The standard evaporator fan motor is factory set  to provide 5 different
fan speeds to choose from for the various operation modes (see Table 4).
All  models  are  factory-shipped  for  nominal  high  stage  and  low  stage
cooling  airflow  operation  at  minimum  external  static  pressure.  See
Table 2.
WARNING
!
EXPLOSION HAZARD
Failure  to  follow  this  warning  could  result  in
death,  serious  personal  injury,  and/or  property
damage.
Never use air or gases containing oxygen for leak
testing  or  operating  refrigerant  compressors.
Pressurized  mixtures  of  air  or  gases  containing
oxygen can lead to an explosion.
WARNING
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in unit damage.
For cooling operation, the recommended airflow is 350 to 450 cfm for
each 12,000 Btuh of rated cooling capacity. For heating operation, the
airflow  must  produce  a  temperature  rise  that  falls  within  the  range
stamped on the unit rating plate.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical  power  to  the unit  and  install  lockout  tag  before
changing blower speed.
Table 3 – Operation Modes and Fan Speeds
208/230 VAC Models
Operation Mode
Fan Speed Tap
Connection
Low Stage Cooling/Heat Pump LOW
High Stage Cooling/Heat Pump HIGH
High Stage Enhanced
 Dehumidification Cooling
DH
Continuous Fan LOW
460 VAC Models
Operation Mode
Fan Speed Tap
Connection
Low Stage Cooling/Heat Pump LOW
High Stage Cooling/Heat Pump HIGH
Continuous Fan LOW
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Disconnect electrical  power  to  the unit  and  install  lockout  tag  before
changing blower speed.