50VR-K: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
Servicing Systems on Roofs with Synthetic Materials 
POE (polyolester) compressor lubricants are known to cause long term
damage  to  some  synthetic  roofing  materials.  Exposure,  even  if
immediately cleaned up, may cause embrittlement (leading to cracking)
to occur in one year or more. When performing any service that may risk
exposure of compressor oil to the roof, take appropriate precautions to
protect roofing. Procedures which risk  oil leakage  include,  but are not
limited to, compressor replacement, repairing refrigerant leaks, replacing
refrigerant  components  such  as  filter  drier,  pressure  switch,  metering
device, coil, accumulator, or reversing valve. 
Synthetic Roof Precautionary Procedure 
1. Cover  extended  roof  working  area  with  an  impermeable
polyethylene (plastic) drip cloth or tarp. Cover an approximate 10 x
10 ft (3 x 3 m) area. 
2. Cover area in front of the unit service panel with a terry cloth shop
towel to absorb lubricant spills, prevent run-offs, and protect drop
cloth from tears caused by tools or components. 
3. Place  terry  cloth  shop  towel  inside  unit  immediately  under
component(s) to be serviced and prevent lubricant run-offs through
the louvered openings in the unit base. 
4. Perform required service. 
5. Remove  and  dispose  of  any  oil  contaminated  material  per  local
codes. 
Liquid Line Filter Drier 
The filter drier is specifically designed to operate with Puron (R-410A).
Use  only  factory-authorized  components.  Filter drier must be replaced
whenever the refrigerant system is opened. When removing a filter drier,
use a tubing cutter to  cut  the  drier from  the system. Do not unsweat a
filter drier from the system. Heat from unsweating will release moisture
and contaminants from drier into system. 
Puron (R-410A) Refrigerant Charging 
Refer  to  unit  information  plate  and  charging  chart.  Some  R-410A
refrigerant cylinders contain a dip tube to allow liquid refrigerant to flow
from cylinder in upright position. For cylinders equipped with a dip tube,
charge  Puron  (R-410A)  units  with  cylinder  in  upright  position  and  a
commercial  metering  device  in  manifold  hose.  Charge  refrigerant  into
suction-line. 
Step 5 – System Information
Loss of Charge Switch
The loss of charge switch is a protective device wired into control circuit
(low voltage).  It  shuts off  the  compressor if  abnormally  low pressures
are present in the refrigeration circuit. 
NOTE:  Because  these  switches  are  attached  to  refrigeration  system
under  pressure,  it  is  not  advisable  to  remove  this  device  for
troubleshooting unless you are reasonably certain that a problem exists.
If switch must be removed, remove and recover all system charge so that
pressure  gauges  read  0  psig.  Never  open  system  without  breaking
vacuum with dry nitrogen.
Check Defrost Thermostat
The  defrost  thermostat  is  usually  located  on  the  lowest  liquid  leaving
circuit of the left condenser coil (see Fig. 23). The thermostat closes at
32_F (0_C) and opens at 65_F (18_C).
The  defrost  thermostat  signals heat  pump  that  conditions  are  right  for
defrost  or  that  conditions  have  changed  to  terminate  defrost.  It  is  a
thermally  actuated  switch  clamped  to  outdoor  coil  to  sense  its
temperature. Normal  temperature range  is  closed  at  32_    3_F  (0  
1.7_C) and open at 65_  5_F (18  2.8_C).
NOTE: The defrost thermostat must be located on the liquid side of the
outdoor coil on the bottom circuit and as close to the coil as possible.
C99029
Fig. 23 – Defrost Thermostat
Troubleshooting
Refer  to  the  Troubleshooting  Chart  (Table 11)  for  troubleshooting
information.
Start-up Checklist
Use the Start-Up Checklist at the back of this manual.
FEEDER TUBE
STUB TUBE
DEFROST
THERMOSTAT