Table 11 – Troubleshooting Chart
SYMPTOM CAUSE REMEDY
Compressor and outdoor fan will not start
Power failure Call power company
Fuse blown or circuit breaker tripped Replace fuse or reset circuit breaker
Defective contactor, transformer or high-pressure,
loss-of-charge or low-pressure switch
Replace component
Insufficient line voltage Determine cause and correct
Incorrect or faulty wiring Check wiring diagram and rewire correctly
Thermostat setting too high
Lower thermostat setting below room
temperature
Compressor will not start but condenser fan runs
Faulty wiring or loose connections in compressor
circuit
Check wiring and repair or replace
Compressor motor burned out, seized, or internal
overload open
Determine cause
Replace compressor
Defective run/start capacitor, overload, start relay Determine cause and replace
Three-phase scroll compressor (size 36-60 unit)
has a low pressure differential
Scroll compressor is rotating in the wrong direction
Correct the direction of rotation by reversing the
3-phase power leads to the unit
Compressor cycles (other than normally
satisfying thermostat)
Refrigerant overcharge or undercharge
Recover refrigerant, evacuate system, and
recharge to capacities shown on rating plate
Defective compressor Replace and determine cause
Insufficient line voltage Determine cause and correct
Blocked condenser Determine cause and correct
Defective run/start capacitor, overload or start relay Determine cause and replace
Defective thermostat Replace thermostat
Faulty condenser-fan motor or capacitor Replace
Restriction in refrigerant system Locate restriction and remove
Compressor operates continuously
Dirty air filter Replace filter
Unit undersized for load Decrease load or increase unit size
Thermostat set too low Reset thermostat
Low refrigerant charge Locate leak, repair, and recharge
Mechanical damage in compressor Replace compressor
Air in system
Recover refrigerant, evacuate system, and
recharge
Condenser coil dirty or restricted Clean coil or remove restriction
Excessive head pressure
Dirty air filter Replace filter
Dirty indoor or outdoor coil Clean coil
Refrigerant overcharged Recover excess refrigerant
Air in system
Recover refrigerant, evacuate system, and
recharge
Head pressure too low
Low refrigerant charge Check for leaks, repair and recharge
Compressor IPR leaking Replace compressor
Restriction in liquid tube Remove restriction
Excessive suction pressure
High heat load Check for source and eliminate
Compressor IPR leaking Replace compressor
Refrigerant overcharged Recover excess refrigerant
Suction pressure too low
Dirty air filter Replace filter
Low refrigerant charge Check for leaks, repair and recharge
Metering device or low side restricted Remove source of restriction
Insufficient evaporator airflow
Increase air quantity
Check filter–replace if necessary
Temperature too low in conditioned area Reset thermostat
Outdoor ambient below 55F (12.7C) Install low-ambient kit
Filter drier restricted Replace filter