50VR-K: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
29
with the proper electrical instrumentation. Refer to the unit wiring label
when making these checkouts. 
NOTE:    Refer  to  the  heating and/or cooling  sequence  of  operation  in
this publication as an aid in determining proper control operation 
Refrigerant Circuit 
Inspect  all  refrigerant  tubing  connections  and  the  unit  base  for  oil
accumulations  annually.  Detecting  oil  generally  indicates  a  refrigerant
leak.
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used  in  this  system.  Gauge  set,  hoses,  and  recovery  system  must  be
designed  to  handle  Puron  (R-410A).  If  you  are  unsure,  consult  the
equipment manufacturer.
If oil is detected or if low cooling performance is suspected, leak-test all
refrigerant  tubing  using  an  electronic  leak-detector,  halide  torch,  or
liquid-soap solution. If a refrigerant leak is detected, refer to Check for
Refrigerant Leaks section. 
If  no  refrigerant  leaks  are  found  and  low  cooling  performance  is
suspected, refer to Checking and Adjusting Refrigerant Charge section. 
Evaporator Airflow 
The  heating  and/or  cooling  air-flow  does  not  require  checking  unless
improper performance is suspected. If a problem exists, be sure that all
supply- and return-air grilles are  open  and free  from  obstructions, and
that the air filter is clean. When necessary, refer to Indoor Airflow and
Airflow Adjustments section to check the system airflow. 
Metering Device
This unit uses 2 types of metering devices. The outdoor metering device
is a fixed orifice and is contained in the brass hex-body in each liquid
line feeding the outdoor coils. The indoor metering device is a TXV type
device.
Pressure Switches 
Pressure  switches  are  protective  devices  wired  into  the  control  circuit
(low  voltage).  They  shut  off  compressor  if  abnormally  high  or  low
pressures are present in the refrigeration circuit. These pressure switches
are specifically designed to operate with Puron (R-410A) systems. R-22
pressure  switches  must  not  be  used  as  replacements  for  the  Puron
(R-410A)air conditioner. 
Loss of Charge Switch
This switch is located on the liquid line and protects against low suction
pressures caused  by  such  events  as  loss  of  charge, low
  airflow  across
indoor coil, dirty filters, etc. It opens on a pressure
 drop at about 20 psig.
If  system  pressure  is  above  this,  switch
  should  be  closed.  To  check
switch:
 
NOTE:  Because  these  switches  are  attached  to  refrigeration  system
under  pressure,  it  is  not  advisable  to  remove  this  device  for
troubleshooting unless you are reasonably certain that a problem exists.
If switch must be removed, remove and recover all system charge so that
pressure gauges read 0 psi (0 Pa). Never open system without breaking
vacuum with dry nitrogen. 
High-Pressure Switch 
The  high-pressure  switch  is  located  in  the  discharge  line  and  protects
against  excessive  condenser  coil  pressure.  It  opens  at  650  psig  (31.1
kPa). High pressure may be caused by a dirty condenser coil, failed fan
motor, or condenser air recirculation. 
To check switch: 
1. Turn off all power to unit. 
2. Disconnect leads on switch. 
3. Apply ohmmeter  leads  across switch. You  should have continuity
on a good switch. 
Copeland Scroll Compressor (Puron [R-410A] 
Refrigerant) 
The compressor used in this product is specifically designed to operate
with Puron (R-410A) refrigerant and cannot be interchanged. 
The compressor is an electrical (as well as mechanical) device. Exercise
extreme caution when working near compressors. Power should be shut
off,  if  possible,  for  most  troubleshooting  techniques.  Refrigerants
present additional safety hazards. 
The  scroll compressor pumps refrigerant throughout the system  by the
interaction of a stationary and an orbiting scroll. The scroll compressor
has  no  dynamic suction  or discharge valves, and  it  is more  tolerant  of
stresses  caused  by  debris,  liquid  slugging,  and  flooded  starts.  The
compressor is equipped with a noise reducing shutdown device and an
internal pressure relief port. The pressure relief port is a safety device,
designed to protect against extreme high pressure. The relief port has an
operating  range  between  550  (26.3  kPa)  and  625  (29.9  kPa)  psig
differential pressure.
Refrigerant 
This system uses Puron (R-410A) refrigerant which has higher operating
pressures than R-22 and other refrigerants. No other refrigerant may be
used  in  this  system.  Gage  set,  hoses,  and  recovery  system  must  be
designed  to  handle  Puron  (R-410A).  If  you  are  unsure,  consult  the
equipment  manufacturer.  Failure  to  use  Puron  (R-410A)  compatible
servicing equipment or replacement components may result in property
damage or injury. 
Compressor Oil 
The Copeland scroll compressor uses 3MAF POE oil. If additional oil is
needed,  use  Uniqema  RL32-3MAF.  If  this  oil  is  not  available,  use
Copeland Ultra 32 CC or Mobil Arctic EAL22 CC. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE oils can absorb 15
times  as  much  water  as  other  oils  designed  for  HCFC  and  CFC
refrigerants. Take all necessary precautions to avoid exposure of the oil
to the atmosphere.
CAUTION
!
EXPLOSION, SAFETY AND ENVIRONMENTAL 
HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
WARNING
!
FIRE/EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death
and/or property damage.
Wear  safety  glasses  and  gloves  when  handling  refrigerants.  Keep
torches and other ignition sources away from refrigerants and oils.
CAUTION
!
EXPLOSION, ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury, death or
equipment damage.
This  system  uses  Puron  (R-410A)  refrigerant  which  has  higher
operating  pressures  than  R-22  and  other  refrigerants.  No  other
refrigerant may be used in this system. Gauge set, hoses, and recovery
system must be designed to handle Puron (R-410A). If you are unsure,
consult the equipment manufacturer.