PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
13
A14532
Fig. 13 – Example of Field Drain Attachment (Not Allowed)
CONDENSATE DRAIN CONNECTION
DO NOT trap the drain line in any other location than at the condensate
drain trap supplied with the furnace. If possible, DO NOT route the drain
line where it may freeze. The drain line must terminate at an inside drain
to prevent freezing of the condensate and possible property damage.
Special  precautions  MUST  be  made  if  installing  furnace  in  an  area
which may drop below 32° F (0° C). This can cause improper operation
or damage to the equipment. If the furnace environment has the potential
of  freezing,  the  drain  trap  and  drain  line  must  be  protected.  In  areas
where the temperature may be below 32° F (0° C), a Condensate Freeze
Protection kit  is required. The kit includes  a condensate trap with heat
pad  and  replaces  the  factory-installed  condensate  trap.  Refer  to  the
Accessory  section  of  the  Product  Data  for  current  kit  number.  A
self-regulating, shielded and waterproof heat tape rated at 3 to 6 watt per
foot (10 to 20  watt per meter)  at 115 volt, 40°F (4°C) may be used to
provide freeze protection of the remaining condensate drain line. Wrap
the  drain  trap  and  drain  line  with  the  heat  tape  and  secure  with
appropriate  plastic  ties.  Follow  the  heat  tape  manufacturer’s
recommendations. Prime the trap before furnace operation.
The  condensate  drain  line  must  be supported  and/or  secured  per  local
codes. Supports and clamps should be spaced to prevent the drain line
from sagging or being dislocated from the furnace or termination point.
In the absence of local codes, consult the current edition of the National
Standard Plumbing Code, in the U.S. or the National Plumbing Code of
Canada in Canada. 
Upflow/Downflow Orientation
In the Upflow or Downflow orientation, the condensate trap is inside the
furnace  casing.  The  condensate  drain  must  be  routed  from  the  trap
through the furnace casing. The condensate drain can be routed through
the left  or right side of the casing. (The left or right side is  as you are
viewing/facing the furnace from the front.)
An indoor coil condensate drain or humidifier drain can be connected to
the external furnace condensate drain provided:
• The drains are not hard piped together, and
• There is an air gap at the point where the two drain lines meet or
• All condensate piping is at least 3/4-in. PVC and there is a relief tee at
the top of condensate drain piping as shown in Fig. 12.
NOTE:  On narrower casings, it may be easier to remove the condensate
trap,  connect  the  drain  line  components  and  re-install  the  condensate
trap. Read the steps thoroughly to familiarize yourself with the required
steps.
For Right Side Condensate Drain:
1. Remove  the  7/8-in.  knockout  or  plug  from  the  right  side  of  the
casing.  See  Fig. 15  for  suggested  knockout  or  plug  removal
technique.
2. Remove the pre-formed rubber drain elbow and two spring clamps
from the loose parts bag.
3. Slide a spring clamp 1-inch (25 mm) down the plain end (the end
without the formed grommet) of the drain elbow.
NOTICE
!
The field-supplied, accessory horizontal drain trap grommet is ONLY
REQUIRED  FOR  DIRECT  VENT  APPLICATIONS.  It  it  NOT
required for applications using single-pipe or ventilated combustion air
venting.
NOTICE
!
The  condensate  trap  extends  below  the  side  of  the  casing  in  the
horizontal  position.  A  minimum  of  2-in.  (51  mm)  of  clearance  is
required between the casing side and the furnace platform for the trap to
extend out of the casing in the horizontal position. Allow at least 1/4-in.
per foot (20 mm per meter) of slope down.
CAUTION
!
FROZEN AND BURST WATER PIPE HAZARD
Failure  to  protect  against  the  risk  of  freezing  may  result  in  property
damage.
Special  precautions  MUST  be  made  if  installing  furnace  in  an  area
which may drop below freezing. This can cause improper operation or
damage  to  equipment.  If  furnace  environment  has  the  potential  of
freezing,  the  drain  trap  and  drain  line  must  be  protected.  The  use  of
accessory drain trap heaters, electric heat tape and/or RV antifreeze is
required for these installations. 
+
+
+
Condensing
Furnace
-
-
-
-
-
Evaporator Coil
+
+
+
< +
< +
< +
+
Blower
-
   + = Positive pressure
< + = Pressure lower than areas with +
 ï = Negative pressure
Blower creates positive pressure.
Positive pressure extends into coil
condensate drain (no trap).
Furnace condensate does not flow
consistently when drain is at positive
pressure.
+
DIRECTION
 
OF
 
AIRFLOW
+
+
+
+
+
+
+
+
+
+
Condensing
Furnace
-
-
-
-
-
Evaporator Coil
+
+
+
< +
< +
< +
+
Blower
-
3/4”
 
PVC
1/2
 
3/4
1/2”
 
CPVC
 
or
 
larger*
   + = Positive pressure
< + = Pressure lower than areas with +
 ï = Negative pressure
+
3/4”
 
PVC
DIRECTION
 
OF
 
AIRFLOW
+
+
+
+
1/2
 
3/4
 
3/4
 
3/4
Open
standpipe
+
+
 
3/4
+
+
+
+
Condensing
Furnace
-
-
-
-
-
Evaporator Coil
+
+
+
< +
< +
< +
+
Blower
-
3/4”
 
PVC
 
3/4
1/2”
 
CPVC
 
or
 
larger*
   + = Positive pressure
< + = Pressure lower than areas with +
 ï = Negative pressure
+
3/4”
 
PVC
DIRECTION
 
OF
 
AIRFLOW
+
+
+
+
 
3/4
 
3/4
 
3/4
 
3/4
 
3/4
+
+
+
+
+
+
+
++
+
CAUTION
!
PROPERTY DAMAGE HAZARD
Failure  to  follow  this  caution  ma  result  in  burst  water  pipes  and/or
property damage.
If a condensate pump is installed, a plugged condensate drain or a failed
pump  may  cause  the  furnace  to  shut  down.  Do  not  leave  the  home
unattended  during  freezing  weather  without  turning  off  water  supply
and  draining  water  pipes  or  otherwise  protecting  against  the  risk  of
frozen pipes