PG96MSA: Installation, Start-up, Operating and Service and Maintenance Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
General Installation 
• US:  NFPA  54/ANSI Z223.1 and the NFPA  90B.  For copies, contact
the  National  Fire  Protection  Association  Inc.,  Batterymarch  Park,
Quincy, MA 02269; or for only the NFPA 54/ANSI Z223.1 contact the
American  Gas Association,  400  N.  Capitol,  N.W.,  Washington  DC
20001 
• CANADA:  NSCNGPIC.  For  a  copy,  contact  Standard  Sales,  CSA
International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario,
M9W 1R3, Canada 
Combustion and Ventilation Air 
• US: Current edition of Section 9.3 of the NFPA54/ANSI Z223.1 Air
for Combustion and Ventilation 
• CANADA:  Current  edition  of  Part  8  of  the  CAN/CSA  B149.1,
Venting Systems and Air Supply for Appliances 
Duct Systems 
• US  and CANADA:  Current edition  of Air Conditioning  Contractors
Association  (ACCA)  Manual  D,  Sheet  Metal  and Air  Conditioning
Contractors  National Association  (SMACNA),  or American  Society
of  Heating,  Refrigeration,  and  Air  Conditioning  Engineers
(ASHRAE) Fundamentals Handbook Chapter 35
Acoustical Lining and Fibrous Glass Duct 
• US and CANADA: Current edition of SMACNA, NFPA 90B as tested
by UL Standard 181 for Class I Rigid Air Ducts 
Gas Piping and Gas Pipe Pressure Testing 
• US: Current edition of NFPA 54/ANSI Z223.1; Chapters 5, 6, 7, and 8
and national plumbing codes.
CANADA: Current edition of CAN/CSA-B149.1, Parts 4, 5, 6, and 9.
In the state of Massachusetts: 
• This product must be installed by a licensed plumber or gas fitter. 
• When  flexible  connectors  are  used,  the  maximum  length  shall  not
exceed 36 in. (914 mm).
• When lever type gas shutoffs are used they shall be T-handle type.
• The use of copper tubing for gas piping is not approved by the state of
Massachusetts. 
Electrical Connections
• US: Current edition of National Electrical Code (NEC) NFPA 70 
• CANADA: Current edition of Canadian Electrical Code CSA C22.1 
Condensate Drain Connection
• US: Current edition of National Standard Plumbing Code, Section 8.7.
• Canada: Current edition of National Plumbing Code of Canada 
ELECTROSTATIC DISCHARGE (ESD) 
PRECAUTIONS PROCEDURE
1. Disconnect all power to the furnace. Multiple disconnects may be
required.  DO  NOT  TOUCH  THE  CONTROL  OR  ANY  WIRE
CONNECTED TO THE CONTROL PRIOR TO DISCHARGING
YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly  touch  the  clean,  unpainted,  metal  surface  of  the  furnace
chassis which is close to the control. Tools held in a person’s hand
during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the control
or  connecting  wires  as  long  as  you  do  nothing  to  recharge  your
body with static electricity (for example; DO NOT move or shuffle
your feet, do not touch ungrounded objects, etc.).
4. If  you  touch  ungrounded  objects  (and  recharge  your  body  with
static electricity), firmly touch a clean, unpainted metal surface of
the furnace again before touching control or wires.
5. Use  this  procedure  for  installed  and  uninstalled  (ungrounded)
furnaces.
6. Before removing a  new control from its container, discharge your
body’s  electrostatic  charge  to  ground  to  protect  the  control  from
damage. If the control is to be installed in a furnace, follow items 1
through 4 before bringing the control or yourself in contact with the
furnace.  Put  all  used  and  new  controls  into  containers  before
touching ungrounded objects. 
7. An ESD service kit (available from commercial sources) may also
be used to prevent ESD damage. 
ACCESSORIES
See Product Data Sheet for a list of accessories for this product.
LOCATION
General 
These  furnaces  are  shipped  with  materials  to  assist  in  proper  furnace
installation.  These  materials  are  shipped  in  the  main  blower
compartment.
See Table 3 for loose parts bag contents.
This furnace must:
• be installed so the electrical components are protected from water.
• not be installed directly on any combustible material other than wood
flooring (refer to SAFETY CONSIDERATIONS).
• be  located  close  to  the  chimney  or  vent  and  attached  to  an  air
distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always comply
with minimum fire protection clearances shown in Table 2 or on the
furnace clearance to combustible construction label. 
The  following  types  of  furnace  installations  may  require  OUTDOOR
AIR for combustion due to chemical exposures:
• Commercial buildings
• Buildings with indoor pools
• Laundry rooms
• Hobby or craft rooms
• Chemical storage areas 
If air is exposed to the following substances,  it should not be used for
combustion air, and outdoor air may be required for combustion:
• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool chemicals
• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as perchloroethylene)
• Printing inks, paint removers, varnishes, etc. 
• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes dryers
• Masonry acid washing materials 
CAUTION
!
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit component damage.
Electrostatic  discharge  can  affect  electronic  components.  Take
precautions  during  furnace  installation  and  servicing  to  protect  the
furnace  electronic  control.  Precautions  will  prevent  electrostatic
discharges  from  personnel  and  hand  tools  which  are  held  during  the
procedure. These precautions will help to avoid exposing the control to
electrostatic  discharge  by  putting  the  furnace,  the  control,  and  the
person at the same electrostatic potential.