Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
44
Access
Value
Point Type
Network
Point
Address
Fire / Smoke Shutdown R
1=Alarm
BI 32 SNVT_switch(95) nvoFrShtdwn
Reset Filter Alarm R/W
1=On
(0)
BO 22 SNVT_switch(95) nviRstFilAlm
ZS Sensor Configuration R
1=Alarm
BI 63 SNVT_switch(95) nvoZsCfgFail
Temperature
R/W °F 45 ADF 16 SNVT_temp_p(105) nviClLckTemp
BAS On / Off R/W
2=Occupied
3=Unoccupied
1 ADI 1 SNVT_count_inc(9) nviBASOnOff
Compressor Status R
1=Alarm
BI 30 SNVT_switch(95) nvoCmpSafety
Timer
R/W hr 600 ADF 28 SNVT_count_inc(9) nviFltAlmTm
Indoor Air Quality Sensor R
1=Alarm
BI 37 SNVT_switch(95) nvoIAQSensor
Temperature
R/W °F 65 ADF 29 SNVT_temp_p(105) nviHtLckTmp
Dehumidification R
1=Active
BI 9
State
R
1=On
BI 20
Min Pos
R/W %Open 20 ADF 60 SNVT_lev_percent(81) nviDCVMinPos
Filter R
1=Dirty
BI 31 SNVT_switch(95) nvoFilter
Safety Chain R
1=Alarm
BI 43 SNVT_switch(95) nvoSftyChain
Setpoint
R/W %rh 95 ADF 59 SNVT_lev_percent(81) nviUnoccRHSP
Supply Air Temp Sensor R
1=Alarm
BI 51 SNVT_switch(95) nvoSATSensor
Remaining
R min ADF 41 SNVT_count_inc(9) nvoOvrTmRem
Setpoint Adjustment R/W
1=Enable
(1)
BO 26 SNVT_switch(95) nviSPAdjEnbl
Temperature
R/W °F -999 ADF 56 SNVT_temp_p(105) nviSysSpTmp
Sensor
R
1=Alarm
BI 27