Appendix A: Network Points List for RTU Open
RTU Open v3 Carrier Proprietary and Confidential CARRIER CORPORATION ©2016
Integration Guide All rights reserved
44
N2
Lonworks
Point Name
Point
Access
Units
Default
Value
N2 Network
Point Type
N2
Network
Point
Address
SNVT Type
SNVT Name
Sensor
1=Alarm
Setpoint Adjustment
R
°F
ADF
44
SNVT_temp_p(105)
nvoSPAdjust
Effective Heat Setpoint
R
°F
ADF
23
SNVT_temp_p(105)
nvoEffHeatSP
Low Fan Econ Min Pos
R/W
%Open
33
ADF
32
SNVT_lev_percent(81)
nviLwFnEcnMn
Fire / Smoke Shutdown R
0=Normal
1=Alarm
BI 32 SNVT_switch(95) nvoFrShtdwn
Reset Filter Alarm R/W
0=Off
1=On
Inactive
(0)
BO 22 SNVT_switch(95) nviRstFilAlm
Setpoint
R/W
°F
ADF
7
SNVT_temp_p(105)
nviUnoccClSP
ZS Sensor Configuration R
0=Normal
1=Alarm
BI 63 SNVT_switch(95) nvoZsCfgFail
Space Relative Humidity
R
%rh
ADF
46
SNVT_lev_percent(81)
nvoSpaceRH
Outdoor Air Temperature
R
°F
ADF
38
SNVT_temp_p(105)
nvoOAT
Cooling Lockout
Temperature
R/W °F 45 ADF 16 SNVT_temp_p(105) nviClLckTemp
Power Exhaust Setpoint
R/W
%Open
50
ADF
43
SNVT_lev_percent(81)
nviPwrExhSP
BAS On / Off R/W
1=Inactive
2=Occupied
3=Unoccupied
1 ADI 1 SNVT_count_inc(9) nviBASOnOff
System Space AQ
R/W
ppm
-999
ADF
39
SNVT_count_inc(9)
nviSysSpAQ
System Space RH
R/W
%
-999
ADF
40
SNVT_lev_percent(81)
nviSysSpRH
Compressor Status R
0=Normal
1=Alarm
BI 30 SNVT_switch(95) nvoCmpSafety
Filter Service Alarm
Timer
R/W hr 600 ADF 28 SNVT_count_inc(9) nviFltAlmTm
Indoor Air Quality Sensor R
0=Normal
1=Alarm
BI 37 SNVT_switch(95) nvoIAQSensor
Heating Lockout
Temperature
R/W °F 65 ADF 29 SNVT_temp_p(105) nviHtLckTmp
Dehumidification R
0=Inactive
1=Active
BI 9
Reversing Valve Relay
State
R
0=Off
1=On
BI 20
Vent Dmpr Pos / DCV
Min Pos
R/W %Open 20 ADF 60 SNVT_lev_percent(81) nviDCVMinPos
Filter R
0=Clean
1=Dirty
BI 31 SNVT_switch(95) nvoFilter
Safety Chain R
0=Normal
1=Alarm
BI 43 SNVT_switch(95) nvoSftyChain
Unocc Relative Humidity
Setpoint
R/W %rh 95 ADF 59 SNVT_lev_percent(81) nviUnoccRHSP
Setpoint
R/W
°F
ADF
9
SNVT_temp_p(105)
nviOccHeatSP
Supply Air Temp Sensor R
0=Normal
1=Alarm
BI 51 SNVT_switch(95) nvoSATSensor
Override Time
Remaining
R min ADF 41 SNVT_count_inc(9) nvoOvrTmRem
Setpoint Adjustment R/W
0=Disable
1=Enable
Active
(1)
BO 26 SNVT_switch(95) nviSPAdjEnbl
System Space
Temperature
R/W °F -999 ADF 56 SNVT_temp_p(105) nviSysSpTmp
System Outdoor AQ
R/W
ppm
-999
ADF
63
Outdoor Air Temp
Sensor
R
0=Normal
1=Alarm
BI 27

Other manuals for Carrier RTU Open v3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier RTU Open v3 and is the answer not in the manual?

Carrier RTU Open v3 Specifications

General IconGeneral
BrandCarrier
ModelRTU Open v3
CategoryController
LanguageEnglish

Related product manuals