19 62-12002
BRIGHT Determines brightness on 
display
Setting is 0 to 100.
SS Parameter
MIN RT Minimum run time for 
perishable setpoints in Start/
Stop mode
4 to 60 minutes, with 1 
minute intervals
Default: 4 minutes
MIN OFF Minimum off time for 
perishable setpoints in Start/
Stop mode
10 to 90 minutes, with 1 
minute intervals
Default: 10 minutes
 OVER Defines how far away the 
active temperature must be 
away from the setpoint before 
the minimum off time can be 
overridden in Start/Stop mode 
for perishable setpoints
36° to 50°F in 0.5° 
increments 
2° to 10°C in 0.1° 
increments.
Default: 39°F (4°C) 
 MAX OFF Maximum off time for 
perishable setpoints during 
Start/Stop mode
0 - Off 
1 - 10 to 255 minutes, with 
1 minute intervals
Default: Off
Mode
LS CON
Determines the low speed 
delay adjustment for 
Continuous
0 - Off
1 - 0 to 255 minutes, with 
1 minute intervals
Default: 1 minute
LS SS
Determines the low speed 
delay adjustment for 
Start/Stop 
mode
0 - Off
1 - 0 to 255 minutes, with 
1 minute intervals
Default: 1 minute
CITY Disable high speed in the 
speed control overrides
0 - Off
1 - On
Default: Off
Only applies to EMEAR 
Region
Functional Parameters (Continued)