19 62-12002
BRIGHT Determines brightness on
display
Setting is 0 to 100.
SS Parameter
MIN RT Minimum run time for
perishable setpoints in Start/
Stop mode
4 to 60 minutes, with 1
minute intervals
Default: 4 minutes
MIN OFF Minimum off time for
perishable setpoints in Start/
Stop mode
10 to 90 minutes, with 1
minute intervals
Default: 10 minutes
OVER Defines how far away the
active temperature must be
away from the setpoint before
the minimum off time can be
overridden in Start/Stop mode
for perishable setpoints
36° to 50°F in 0.5°
increments
2° to 10°C in 0.1°
increments.
Default: 39°F (4°C)
MAX OFF Maximum off time for
perishable setpoints during
Start/Stop mode
0 - Off
1 - 10 to 255 minutes, with
1 minute intervals
Default: Off
Mode
LS CON
Determines the low speed
delay adjustment for
Continuous
0 - Off
1 - 0 to 255 minutes, with
1 minute intervals
Default: 1 minute
LS SS
Determines the low speed
delay adjustment for
Start/Stop
mode
0 - Off
1 - 0 to 255 minutes, with
1 minute intervals
Default: 1 minute
CITY Disable high speed in the
speed control overrides
0 - Off
1 - On
Default: Off
Only applies to EMEAR
Region
Functional Parameters (Continued)