62-12002 20
Other
DEFR The time interval between
defrost cycles
0 - 1.5 hours
1 - 3 hours
2 - 6 hours
3 - 12 hours
Default: 6 Hours
SWT DSL Switch to Diesel: When this
functional parameter indicates
No, the No Power
configuration parameter is
overridden and the system
can be shut down.
0 - No
1 - Yes
Default: No
FRESHNO Fresh Protect: Used for supply
air control.
0 - OFF
1 - A
2 - B
3 - C (Default)
4 - D
5 - E
TRANGE Out-of-range temperature
tolerance selection.
0 - Off
1 - 2°C (NDTP Display A)
2 - 3°C (NDTP Display B)
3 - 4°C (NDTP Display C)
Default: 4°C
OVR DOOR Indicates if the door switch
alarm should override the
shutdown of the unit. If the
Override Door switch
Shutdown functional
parameter = Yes, the door
switch alarm controller
response is alarm only
regardless of the configuration
parameter. Low speed Alarm
only could still be applicable.
0 - No
1 - Yes
Default: No
Functional Parameters (Continued)