Energy Monitoring Menu – ENERGY
No. Name Status Unit Displayed text* Description
1 coolPowT - kW Cooling Power Total Cooling power (circuit A + circuit B)
2 powIn - kW Electrical Power input Electrical power input of compressors and fans
(estimated if EC fans are selected)
3 eer - - Energy Eciency Energy eciency (circuit A + circuit B)
4
5 energOut - kWh Cooling Energy output Cooling energy output
6 energyIn - kWh Electrical Energy input Electrical energy input of compressors and fans
(estimated if EC fans are selected)
7 energEER - - Integrated EER Integrated EER (Energy Eciency Ratio)
8 reset_en no/yes - Reset energy counter Used to reset energy counter
9 reset_da - - Last Reset Date Last reset date
10 reset_ti - - Last Reset time Last reset time
11
12 powPmp - kW Pump Elec Power Input Pump electric power input
13 energyP - kWh Pump Elec Energy Input Pump electric energy input
14 resetpmp no/yes - Reset pump energy Used to reset pump energy counter
15 pmp_date - - Pump Last Reset Date Last reset date (pump)
16 pmp_time - - Pump Last Reset time Last reset time (pump)
*Depends on the selected language (English by default).
Setpoint Menu – SETPOINT
No. Name Status Default Unit Displayed text* Description
1 csp1 -28.9 to 26 6.7 °C Cooling Setpoint 1 Cooling setpoint 1 (used during occupied periods)
2 csp2 -28.9 to 26 6.7 °C Cooling Setpoint 2 Cooling setpoint 2 (used during unoccupied periods)
3 ice_sp -28.9 to 26 6.7 °C Cooling Ice Setpoint Ice storage setpoint
4 cramp_sp 0.1 to 11.1 0.5 K Cooling Ramp Loading Cooling ramp loading setpoint
(rate at which the water temperature may change
within one minute in Cooling mode)
5 hsp1 26.7 to 63 37.8 °C Heating Setpoint 1 Not applicable to this unit
6 hsp2 26.7 to 63 37.8 °C Heating Setpoint 2 Not applicable to this unit
7 hramp_sp 0.1 to 11.1 0.5 K Heating Ramp Loading Not applicable to this unit
8 cauto_sp 3.9 to 50 23.9 °C Cool Changeover Setpt Not applicable to this unit
9 hauto_sp 0 to 46 17.8 °C Heat Changeover Setpt Not applicable to this unit
10 vpmpdtsp 1 to 29 5 K Varipump Delta Temp
Stp
Variable speed pump, water flow based on
delta T control
11 vpmpdpsp 50 to 620 200 kPa Varipump Pressure Stp Variable speed pump pressure setpoint
12 lim_sp1 0 to 100 100 % Switch Limit Setpoint 1 Demand limit setpoint 1
13 lim_sp2 0 to 100 100 % Switch Limit Setpoint 2 Demand limit setpoint 2
14 lim_sp3 0 to 100 100 % Switch Limit Setpoint 3 Demand limit setpoint 3