TOUCH PILOT CONTROL: DETAILED MENU STRUCTURE
7.1 - Main menu
Icon Displayed text* Description Associated table
General Parameters General parameters GENUNIT
Temperatures Temperatures TEMP
Pressures Pressures PRESSURE
Inputs Status Inputs status INPUTS
Outputs Status Outputs status OUTPUTS
Pump Status Pump status PUMPSTAT
Run Times Run times RUNTIME
Modes Modes MODES
Setpoint Table Setpoints SETPOINT
Energy monitoring Energy monitoring ENERGY
Conguration Menu
Conguration menu
(see section 7.2)
CONFIG
Trendings Trendings ** TRENDING
* Depends on the selected language (English by default).
** The Trendings menu is displayed in form of a graph. For more information about Trendings, see section 5.9.
CAUTION: Since specic units may not include additional features, some tables may contain parameters that cannot be
congured for a given unit.
General Parameters Menu – GENUNIT
No. Name Status Unit Displayed text* Description
1 CTRL_TYP 0 to 2 - Local=0 Net.=1 Remote=2 Operating mode:
0 = Local
1 = Network
2 = Remote
2 STATUS - - Run Status O, Running, Stopping, Delay, Trip out, Ready,
Override, etc.
3 CHIL_S_S disable/enable - Net.: Cmd Start/Stop Unit start/stop via Network: When the unit is in
Network mode, start/stop command can be forced
4 CHIL_OCC no/yes - Net.: Cmd Occupied Unit time schedule via Network: When the unit is in
Network mode, the forced value can be used instead
of the real occupancy state
5 min_left - min Minutes Left for Start Minutes before the unit start-up
6 HEATCOOL Cool Heat/Cool status Heating/cooling status: 30KAV are cooling-only
chillers ("heating" is NOT available)
7 HC_SEL 0 to 2 - Heat/Cool Select Heating/cooling selection (only cooling mode is allowed)
8 0=Cool. 1=Heat. 2=Auto 0 = Cooling mode
1,2 = not applicable to this unit