28
Start-up delay
When changing the operating type (Local/Remote/Network),
the control normally undergoes the transition stage during
which the unit is stopped, and then allowed to start again
(start-up delay is applied).
Unit stop function
This function controls the unit compressor capacity reduction.
If there is an alarm or a demand to stop, it forces the
compressors to the minimum capacity before stopping them.
TOUCH PILOT CONTROL OPERATION
8.1 - Start / Stop control
The unit state is determined based on a number of factors,
including its operating type, active overrides, open contacts,
master/slave configuration, or alarms triggered due to
operating conditions.
The table given below summarises the unit control type
[ctrl_typ] and its running status with regard to the following
parameters:
• Operating type: Operating type is selected using the
Start/Stop button on the user interface.
LOFF Local o
L-C Local on
L-SC Local schedule
Rem Remote
Net Network
Mast Master unit
Active operating type Parameters status
Control
type
Unit
state
LOFF L-C L-SC Rem Net Mast
Start/Stop
force
command
Remote
start/stop
contact
Master
control
type
Start/Stop
schedule
Network
Emergency
Shutdown
Alarm
shutdown
- - - - - - - - - enabled - - o
- - - - - - - - - - - yes - o
active - - - - - - - - - - - local o
- - active - - - - - - unoccupied - - local o
- - - active - - - open - - - - remote o
- - - active - - - - - unoccupied - - remote o
- - - - active - disabled - - - - - network o
- - - - active - - - - unoccupied - - network o
- - - - - active - - local unoccupied - - local o
- - - - - active - open remote - - - remote o
- - - - - active - - remote unoccupied - - remote o
- - - - - active disabled - network - - - network o
- - - - - active - - network unoccupied - - network o
- active - - - - - - - - disabled no local on
- - active - - - - - - occupied disabled no local on
- - - active - - - closed - occupied disabled no remote on
- - - - active - enabled - - occupied disabled no network on
- - - - - active - - local occupied disabled no local on
- - - - - active - closed remote occupied disabled no remote on
- - - - - active enabled - network occupied disabled no network on
• Start/stop force command [CHIL_S_S]:
Unit start/stop force command can be used to control
the unit state in the Network operating type.
Command set to stop: The unit is halted.
Command set to start: The unit runs according to
schedule 1.
• Remote start/stop contact status [Onoff_sw]:
Start/stop contact can be used to control the unit state
in the Remote operating type.
• Master control type [ms_ctrl]: When the unit is the
master unit in a two-unit master/slave arrangement,
the master unit may be set to be controlled locally,
remotely or via network.
• Start/stop schedule [chil_occ]: Occupied or unoccupied
status of the unit.
• Network emergency stop command [EMMSTOP]:
If activated, the unit shuts down regardless of the active
operating type.
• General alarm: The unit shuts down due to failure.
IMPORTANT: When the unit is stopping or there is a demand
to stop the unit, compressors are stopped consecutively.
In case of emergency stop, all compressors are stopped at
the same time.