23
7.2 - Conguration menu
Icon Displayed text* Description Associated table
General Conguration General conguration GEN_CONF
Pump Conguration Pump conguration PUMPCONF
User Conguration User conguration USERCONF
Reset Conguration Reset conguration RESETCFG
Schedule Menu Schedule menu SCHEDULE
Holiday Menu Holiday menu HOLIDAY
Broadcast Menu Broadcast menu BROCASTS
Date/Time Conguration Date/Time conguration DATETIME
Control Identication Control identication CTRL_ID
Connection cong Web connection conguration CONNECT
*Depends on the selected language (English by default).
CAUTION: Since specic units may not include additional features, some tables may contain parameters that cannot be
congured for a given unit.
General Conguration Menu – GEN_CONF
No. Name Status Default Unit Displayed text* Description
1 prio_cir 0 to 2 0 - Cir Priority Sequence Circuit priority
2 0=Auto, 1=A Prio 0 = Automatic circuit selection
1 = Circuit A priority
3 2=B Prio 2 = Circuit B priority
4 seq_typ no/yes no - Staged Loading Sequence Loading sequence:
no = Equal loading sequence
yes = Staged loading sequence
5 ramp_sel no/yes no - Ramp Loading Select Ramp loading selection
6 transcap 30 to 80 50 % Cap. to start 2nd cir Capacity required in order to start the second
circuit
7 o_on_d 1 to 15 1 min Unit O to On Delay Unit O to On delay
8 lim_sel 0 to 2 0 - Demand Limit Type Select Demand limit selection
9 0 = None 0 = None
10 1 = Switch Control 1 = Switch Control
11 2 = 4-20mA Control 2 = 4-20mA Control
12 nh_start 00:00 00:00 - Night Mode Start Hour Night mode start hour (compressor capacity is
reduced during the night mode)
13 nh_end 00:00 00:00 - Night Mode End Hour Night mode end hour
14 nh_limit 0 to 100 100 % Night Capacity Limit Night capacity limit
15 pow_sel no/yes no - Power Limit select Not applicable to this unit
16 ice_cnfg no/yes no - Ice Mode Enable Ice mode enabled
17 pow_max 0 to 2000 2000 kW Maximum Power Limit Not applicable to this unit
18 shortcyc no/yes no - short cycle management Short cycle management