7.2 - Conguration menu
Icon Displayed text* Description Associated table
General Conguration General conguration GEN_CONF
Pump Conguration Pump conguration PUMPCONF
User Conguration User conguration USERCONF
Reset Conguration Reset conguration RESETCFG
Schedule Menu Schedule menu SCHEDULE
Holiday Menu Holiday menu HOLIDAY
Broadcast Menu Broadcast menu BROCASTS
Date/Time Conguration Date/Time conguration DATETIME
Control Identication Control identication CTRL_ID
Connection cong Web connection conguration CONNECT
*Depends on the selected language (English by default).
CAUTION: Since specic units may not include additional features, some tables may contain parameters that cannot be
congured for a given unit.
General Conguration Menu – GEN_CONF
No. Name Status Default Unit Displayed text* Description
1 prio_cir 0 to 2 0 - Cir Priority Sequence Circuit priority
2 0=Auto, 1=A Prio 0 = Automatic circuit selection
1 = Circuit A priority
3 2=B Prio 2 = Circuit B priority
4 seq_typ no/yes no - Staged Loading Sequence Loading sequence:
no = Equal loading sequence
yes = Staged loading sequence
5 ramp_sel no/yes no - Ramp Loading Select Ramp loading selection
6 transcap 30 to 80 50 % Cap. to start 2nd cir Capacity required in order to start the second
circuit
7 o_on_d 1 to 15 1 min Unit O to On Delay Unit O to On delay
8 lim_sel 0 to 2 0 - Demand Limit Type Select Demand limit selection
9 0 = None 0 = None
10 1 = Switch Control 1 = Switch Control
11 2 = 4-20mA Control 2 = 4-20mA Control
12 nh_start 00:00 00:00 - Night Mode Start Hour Night mode start hour (compressor capacity is
reduced during the night mode)
13 nh_end 00:00 00:00 - Night Mode End Hour Night mode end hour
14 nh_limit 0 to 100 100 % Night Capacity Limit Night capacity limit
15 pow_sel no/yes no - Power Limit select Not applicable to this unit
16 ice_cnfg no/yes no - Ice Mode Enable Ice mode enabled
17 pow_max 0 to 2000 2000 kW Maximum Power Limit Not applicable to this unit
18 shortcyc no/yes no - short cycle management Short cycle management