General Parameters Menu – GENUNIT (continued)
No. Name Status Unit Displayed text* Description
9 SP_SEL 0 to 2 - Setpoint Select Setpoint selection
10 0=Auto. 1=Spt1. 2=Spt2 0 = Auto (schedule control)
1 = Setpoint 1 (active during occupied period)
2 = Setpoint 2 (active during unoccupied period)
11 SP_OCC no/yes - Setpoint Occupied? Current setpoint
12 CAP_T - % Percent Total Capacity Total unit capacity
13 CAPA_T - % Cir A Total Capacity Circuit A capacity
14 CAPB_T - % Cir B Total Capacity Circuit B capacity
15 SP - °C Current Setpoint Current setpoint
16 CTRL_PNT -20 to 67.2 °C Control Point Control point: Water temperature that the unit must
produce (active setpoint + reset)
17 TOT_CURR - A Actual Chiller Current Actual chiller current
18 POW_LIM 0 to 2000 kW Chiller Power Limit Chiller power limit
19 COOL_POW - kW Cool. Power (kit hydro) Cooling power (optional hydronic kit)
20 EMSTOP disable/enable - Emergency Stop Emergency stop: Used to stop the unit regardless of
its active operating type
21 DEM_LIM 0 to 100 % Active Demand Limit Val Active demand limit value: When the unit is in Network
mode, the minimum value will be used compared to
the status of the external limit switch contact and the
demand limit switch setpoint
*Depends on the selected language (English by default).
Temperatures Menu – TEMP
No. Name Status Unit Displayed text* Description
1 COOL_EWT - °C Cooler Entering Fluid Evaporator entering uid temperature:
Used for capacity control
2 COOL_LWT - °C Cooler Leaving Fluid Evaporator leaving uid temperature:
Used for capacity control
3 OAT - °C Outdoor Air Temperature Outdoor air temperature
4 SCT_A - °C Saturated Cond Tmp cir A Saturated condensing temperature, circuit A
5 SST_A - °C Saturated Suction Temp A Saturated suction temperature, circuit A
6 SLT_A - °C Saturated Liquid Temp A Saturated liquid temperature, circuit A
7 SUCT_A - °C Compressor Suction Tmp A Compressor suction temperature, circuit A
8 DGT_A - °C Discharge Gas Temp cir A Discharge gas temperature, circuit A
9 CP_TMP_A - °C Motor Temperature cir A Motor temperature, circuit A
10 ECO_T_A - °C EXV Eco. Tmp cir A EXV economizer temperature, circuit A
11 LIQ_T_A - °C Liquid Temperature A Liquid temperature, circuit A
12 SCT_B - °C Saturated Cond Tmp cir B Saturated condensing temperature, circuit B
13 SST_B - °C Saturated Suction Temp B Saturated suction temperature, circuit B
14 SLT_B - °C Saturated Liquid Temp B Saturated liquid temperature, circuit B
15 SUCT_B - °C Compressor Suction Tmp B Compressor suction temperature, circuit B
16 DGT_B - °C Discharge Gas Temp cir B Discharge gas temperature, circuit B
17 CP_TMP_B - °C Motor Temperature cir B Motor temperature, circuit B
18 ECO_T_B - °C EXV Eco. Tmp cir B EXV economizer temperature, circuit B
19 LIQ_T_B - °C Liquid Temperature B Liquid temperature, circuit B
20 SPACETMP - °C Optional Space Temp Optional space temperature (EMM option)
21 CHWSTEMP - °C CHWS Temperature Master/Slave common water temperature
22 T_HEATER - °C Cooler Heater Temp Evaporator heater temperature
*Depends on the selected language (English by default).