19
Pressures Menu – PRESSURE
No. Name Status Unit Displayed text* Description
1 DP_A - kPa Discharge Pressure A Discharge pressure, circuit A
2 SP_A - kPa Main Suction Pressure A Main suction pressure, circuit A
3 OP_A - kPa Oil Pressure A Oil pressure, circuit A
4 DOP_A - kPa Oil Pressure DierenceA Oil Pressure dierence, circuit A
5 ECO_P_A - kPa Economizer Pressure A Economizer pressure, circuit A
6 LIQ_P_A - kPa Liquid Pressure A Liquid pressure, circuit A
7 DP_B - kPa Discharge Pressure B Discharge pressure, circuit B
8 SP_B - kPa Main Suction Pressure B Main suction pressure, circuit B
9 OP_B - kPa Oil Pressure B Oil pressure, circuit B
10 DOP_B - kPa Oil Pressure DierenceB Oil Pressure dierence, circuit B
11 ECO_P_B - kPa Economizer Pressure B Economizer pressure, circuit B
12 LIQ_P_B - kPa Liquid Pressure B Liquid pressure, circuit B
13 EWATPRES - kPa Entering water pressure Entering water pressure
14 LWATPRES - kPa Leaving water pressure Leaving water pressure
15 WATPRES3 - kPa Water pressure 3 Not applicable to this unit
16 WATPRES4 - kPa Water pressure 4 Not applicable to this unit
*Depends on the selected language (English by default).
Inputs Status Menu – INPUTS
No. Name Status Unit Displayed text* Description
1 ONOFF_SW open/close - Remote On/O Switch Remote on/o switch
2 SETP_SW open/close - Remote Setpoint Switch Remote cooling setpoint selection switch
3 LIM_SW1 open/close - Limit Switch 1 Demand limit switch 1
4 LIM_SW2 open/close - Limit Switch 2 Demand limit switch 2 (EMM option)
5 OIL_L_A open/close - Oil Level Input A Oil level input, circuit A
6 OIL_L_B open/close - Oil Level Input B Oil level input, circuit B
7 SP_RESET - mA Reset/Setpnt4-20mA Sgnl 4-20 mA signal, setpoint reset
8 LIM_ANAL - mA Limit 4-20mA Signal 4-20 mA signal, capacity limit
9 leak_v - V Leakage detector 1 val Refrigerant leakage detection (optional)
10 leak_2_v - V Leakage detector 2 val Refrigerant leakage detection (optional)
11 REM_LOCK open/close - Customer Interlock Customer interlock: When the contact is closed, the unit
will be stopped with no delay. The switch is provided on
the customer's terminal block of the optional EMM.
12 ICE_SW open/close - Ice Done Storage Switch Ice storage end switch
13 OCC_OVSW open/close - Occupied Override Switch Occupied override switch
14 RECL_SW open/close - Remote Reclaim switch Remote reclaim switch
15 ELEC_BOX open/close - Electrical box Interlock Electrical box interlock
16 HEATR_SW open/close - Cooler Heater Detector Evaporator heater
17 bacdongl no/yes - BACnet dongle BACnet dongle: Used when the unit is incorporated
into the BACnet network
*Depends on the selected language (English by default).
Outputs Status Menu – OUTPUTS
No. Name Status Unit Displayed text* Description
1 CP_A o/on - Compressor A Compressor A status
2 OIL_SL_A o/on - Oil Solenoid Output A Oil solenoid output, circuit A
3 CAPT010A 0 to 10 V Capacity Signal Cir A 0-10V capacity signal, circuit A
4 VFAN_A 0 to 100 % VariFan Speed A Variable speed fan, circuit A
5 ISO_CL_A o/on - Ref Iso Valve Close A Refrigerant isolation valve closed, circuit A