15
Fig. 18 — Powered Convenience Outlet Wiring
DUTY CYCLE
The unit-powered convenience outlet has a duty cycle limitation.
The transformer is intended to provide power on an intermittent
basis  for service  tools,  lamps,  etc; it  is  not intended  to provide
15 amps loading for continuous duty loads (such as electric heat-
ers  for  overnight  use).  Observe  a  50%  limit on  circuit  loading
above 8 amps (i.e., limit loads exceeding 8 amps to 30 minutes of
operation every hour).
MAINTENANCE
Periodically test the GFCI receptacle by pressing the TEST button
on the face of the receptacle. This should cause the internal circuit
of the receptacle to trip and open the receptacle. Check for proper
grounding  wires and power line phasing if the GFCI receptacle
does  not  trip  as required.  Press  the  RESET  button  to  clear the
tripped condition.
FUSE ON POWERED TYPE
The factory fuse is a Bussman
1
 “Fusetron” T-15, non-renewable
screw-in (Edison base) type plug fuse.
USING UNIT-MOUNTED CONVENIENCE OUTLETS
Units with unit-mounted convenience outlet circuits will often re-
quire that two disconnects be opened to de-energize all power to
the unit. Treat all units as electrically energized until the conve-
nience  outlet  power is also  checked and de-energization is con-
firmed. Observe National Electrical Code Article 210, Branch Cir-
cuits, for use of convenience outlets.
SMOKE DETECTORS
Smoke  detectors  are  available  as  factory-installed  options  on
48LC models. Smoke detectors may be specified for supply air
only, for return air without or with economizer, or in combination
of  supply  air  and  return  air.  Return-air smoke  detectors  are  ar-
ranged  for  vertical  return  configurations  only. All  components
necessary  for  operation  are  factory-provided and  mounted.  The
unit is factory-configured for immediate smoke detector shutdown
operation;  additional  wiring  or  modifications  to  unit  terminal
board may be necessary to complete the unit and smoke detector
configuration to meet project requirements.
System
The smoke detector system consists of a four-wire controller and
one or two sensors. Its primary function is to shut down the roof-
top unit in order to prevent smoke from circulating throughout the
building. It is not to be used as a life saving device.
Controller
The controller (see Fig. 19) includes a controller housing, a print-
ed circuit board, and a clear plastic cover. The controller can be
connected to one or two compatible duct smoke sensors. The clear
plastic cover is secured to the housing with a single captive screw
for easy access to the wiring terminals. The controller has three
LEDs (for Power, Trouble and Alarm) and a manual test/reset but-
ton (on the cover face).
Fig. 19 — Controller Assembly
Sensor
The sensor (see Fig. 20) includes a plastic housing, a printed cir-
cuit board, a clear plastic cover, a sampling tube inlet and an ex-
haust tube. The sampling tube (when used) and exhaust tube are
attached during installation. The sampling tube varies in length de-
pending on the size of the rooftop unit. The clear plastic cover per-
mits visual inspections without having to disassemble the sensor.
The cover attaches to the sensor housing using four captive screws
and  forms  an  airtight  chamber  around  the  sensing  electronics.
Each sensor includes a harness with an RJ45 terminal for connect-
ing to the controller. Each sensor has four LEDs (for Power, Trou-
ble, Alarm and Dirty) and a manual test/reset button (on the left-
side of the housing).
Air  is  introduced  to  the  duct  smoke  detector  sensor’s  sensing
chamber through a sampling tube that extends into the HVAC duct
and is directed back into the ventilation system through a (shorter)
exhaust tube.
The difference in air pressure between the two tubes pulls the sam-
pled air through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor signals an
alarm state and the controller automatically takes the appropriate
1. Bussmann is a trademark of Cooper Technologies Company.
UNIT
VOLTAGE
CONNECT
AS
PRIMARY
CONNECTIONS
TRANSFORMER
TERMINALS
208, 230 240
L1: RED +YEL
L2: BLU + GRA
H1 + H3
H2 + H4
460 480
L1: RED
Splice BLU + YEL
L2: GRA
H1
H2 + H3
H4
575 600
L1: RED
L2: GRA
H1
H2
DUCT SMOKE SENSOR
CONTROLLER
CONDUIT NUTS
(SUPPLIED BY INSTALLER)
CONDUIT SUPPORT PLATE
TERMINAL BLOCK COVER
COVER GASKET
(ORDERING OPTION)
CONTROLLER 
COVER
FASTENER (2X)
CONDUIT COUPLINGS
(SUPPLIED BY INSTALLER)
CONTROLLER HOUSING
AND ELECTRONICS
ALARM
TROUBLE
POWER
TEST/RESET
SWITCH