EasyManua.ls Logo

Carrier WeatherExpert 48LCD05 - Page 28

Carrier WeatherExpert 48LCD05
76 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
28
Table 9 — IGC Connections
TERMINAL LABEL POINT DESCRIPTION SENSOR LOCATION TYPE OF I/O
CONNECTION
PIN NUMBER
INPUTS
RT, C Input power from TRAN 1 control box 24 VAC
SS Speed sensor gas section analog input J1, 1-3
FS, T1 Flame sensor gas section switch input
W Heat stage 1 LCTB 24 VAC J2, 2
RS Rollout switch gas section switch input J2, 5-6
LS Limit switch fan section switch input J2, 7-8
CS Centrifugal switch (not used) switch input J2, 9-10
OUTPUTS
L1, CM Induced draft combustion motor gas section line VAC
IFO Indoor fan control box relay J2, 1
GV Gas valve (heat stage 1) gas section relay J2, 11-12
Table 10 — Orifice Sizes
ORIFICE
DRILL SIZE
CARRIER
PART NUMBER
DRILL
DIA. (in.)
#30 LH32RF129 0.1285
1/8 LH32RF125 0.1250
#31 LH32RF120 0.1200
#32 LH32RF116 0.1160
#33 LH32RF113 0.1130
#34 LH32RF111 0.1110
#35 LH32RF110 0.1100
#36 LH32RF105 0.1065
#37 LH32RF104 0.1040
#38 LH32RF102 0.1015
#39 LH32RF103 0.0995
#40 LH32RF098 0.0980
#41 LH32RF096 0.0960
#42 LH32RF094 0.0935
#43 LH32RF089 0.0890
#44 LH32RF086 0.0860
#45 LH32RF082 0.0820
#46 LH32RF080 0.0810
#47 LH32RF079 0.0785
#48 LH32RF076 0.0760
#49 LH32RF073 0.0730
#50 LH32RF070 0.0700
#51 LH32RF067 0.0670
#52 LH32RF065 0.0635
#53 LH32RF060 0.0595
#54 LH32RF055 0.0550
#55 LH32RF052 0.0520
#56 LH32RF047 0.0465
#57 LH32RF043 0.0430
#58 LH32RF042 0.0420