40
STATUS
(cont)
EXH2 OUT OFF ON/OFF
EXHAUST STAGE 2 RELAY OUTPUT
Output of AUX1 O terminal
Displays ON when damper position reaches programmed 
percentage set point.
ON = 24 vac output
OFF = No output
Displays only if AUX1 O = EXH2
ERV OFF ON/OFF
ENERGY RECOVERY VENTILATOR
Output of AUX1 O terminal; displays only if AUX1 O = ERV
ON = 24 vac output
OFF = No Output
MECH COOL ON
or
HEAT STAGES ON
0 0, 1, or 2
Displays stage of mechanical cooling that is active.
Displays the stage of heat pump heating that is active.
FAN SPEED N/A LOW or HIGH
SUPPLY FAN SPEED
Displays speed setting of fan on a 2-speed fan unit.
W (HEAT IN) N/A ON/OFF
HEAT DEMAND STATUS
Displays status of heat demand on a 2-speed fan unit.
SETPOINTS
MAT SET 53°F (12°C)
38°F to 70°F
(3°C to 21°C);
increment by 1 
degree
SUPPLY AIR SETPOINT
The economizer will modulate the OA damper to maintain the 
mixed air temperature at the set point
LOW T LOCK 32°F (0°C)
–45°F to 80°F
(–43°C to 27°C);
increment by 1°F
COMPRESSOR LOW TEMPERATURE LOCKOUT
Set point determines outdoor temperature when the mechanical 
cooling cannot be turned on. Commonly referred to as the 
Compressor lockout. At or below the set point, the Y1-O and Y2-O 
will not be energized on the controller.
DRYBLB SET 63°F (17°C)
48°F to 80°F
(9°C to 27°C);
increment by 1°F
OA DRY BULB TEMPERATURE CHANGEOVER SETPOINT
Dry bulb set point will only appear if using dry bulb changeover.
Set point determines where the economizer will assume outdoor 
air temperature is good for free cooling; e.g.; at 63°F unit will 
economize at 62°F and below and not economize at 64°F and 
above. There is a 2°F deadband.
ENTH CURVE ES3
ES1,ES2,ES3,ES4, 
or ES5
ENTHALPY CHANGEOVER CURVE
ES curve will only appear if using enthalpy changeover.
Enthalpy boundary “curves” for economizing using single 
enthalpy. See page 45 for description of enthalpy curves.
DCV SET 1100ppm
500 to 2000 ppm; 
increment by 100
DEMAND CONTROLLED VENTILATION
Displays only if CO
2
 sensor is connected. Set point for Demand 
Controlled Ventilation of space. Above the set point, the OA 
dampers will modulate open to bring in additional OA to maintain 
a space ppm level below the set point.
MIN POS 2.8 V 2 to 10 vdc
VENTILATION MINIMUM POSITION
Displays ONLY if a CO
2
 sensor is NOT connected.
VENTMAX  2.8 V
2 to 10 vdc
DCV MAXIMUM DAMPER POSITION
Displays only if a CO
2
 sensor is connected.
Used for Vbz (ventilation max cfm) set point. VENTMAX is the 
same setting as MIN POS would be if unit did not have CO
2
 
sensor.
100 to 9990 cfm; 
increment by 10
If OA, MA, RA, and CO
2
 sensors are connected and DCV CAL 
ENABLE is set to AUTO mode, the OA dampers are controlled 
by CFM and displays from 100 to 9990 CFM.
2 to 10 vdc
With 2-speed fan units, VENTMAX L (low speed fan) and 
VENTMAX H (high speed fan) settings are required. Default for 
VENTMAX L is 3.2V and VENTMAX H is 2.8V
VENTMIN  2.25 V
2 to 10 vdc or 100 
to 9990 cfm 
increment by 10
DCV MINIMUM DAMPER POSITION
Displays only if a CO
2 
sensor is connected. Used for Va 
(ventilation min cfm) set point. This is the ventilation for less than 
maximum occupancy of the space.
100 to 9990 cfm; 
increment by 10
If OA, MA, RA, and CO
2
 sensors are connected and DCV CAL 
ENABLE is set to AUTO mode, the OA dampers are controlled 
by CFM and displays from 100 to 9990 CFM.
2 to 10 vdc
With 2-speed fan units VENTMIN L (low speed fan) and 
VENTMIN H (high speed fan) settings are required. Default for 
VENTMIN L is 2.5V and VENTMIN H is 2.25V
ERV OAT SP
††
32°F (0°C)
0°F to 50°F
(–18°C to 10°C);
increment by 1°F
ENERGY RECOVERY VENTILATOR UNIT OUTDOOR AIR 
TEMPERATURE SETPOINT
Only when AUX1 O = ERV
EXH1 SET 50%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 1 SETPOINT
Set point for OA damper position when exhaust fan 1 is powered 
by the economizer.
EXH2 SET 75%
0 to 100%;
increment by 1
EXHAUST FAN STAGE 2 SETPOINT
Set point for OA damper position when exhaust fan 2 is powered 
by the economizer. Only used when AUX1 O is set to EHX2.
Table 19 — W7220 Menu Structure* (cont)
MENU PARAMETER
PARAMETER 
DEFAULT 
VALUE
PARAMETER 
RANGE AND 
INCREMENT
†
EXPANDED PARAMETER NAME
Notes