APPENDIX A — LOCAL DISPLAY TABLES (cont)
MODE — CONFIGURATION (cont)
ITEM EXPANSION RANGE UNITS CCN POINT DEFAULT PAGE NO.
IAQ INDOOR AIR QUALITY CFG.
DCV.C DCV ECONOMIZER SETPOINTS
DCV.CEC.MN Economizer Min.Position 0 to 100 % ECONOMIN 5 40,41,83-85
DCV.CIAQ.M
IAQ Demand Vent Min.Pos. 0 to 100 % IAQMINP 0 28,40,41, 83-
86,123
DCV.CO.C.MX Economizer Min.Flow 0 to 20000 CFM OACFMMAX 2000 28,40,85
DCV.CO.C.MN IAQ Demand Vent Min.Flow 0 to 20000 CFM OACFMMIN 0 28,40,85
DCV.CO.C.DB Econ.Min.Flow Deadband 200 to 1000 CFM OACFM_DB 400 85
AQ.CF AIR QUALITY CONFIGS
AQ.CFIQ.A.C
IAQ Analog Sensor Config 0 to 4 IAQANCFG 0 40,41,45,83,
85
AQ.CFIQ.A.F IAQ 4-20 ma Fan Config 0 to 2 IAQANFAN 0 40,83,85
AQ.CFIQ.I.C IAQ Discrete Input Confg 0 to 2 IAQINCFG 0 40,45,84,85
AQ.CFIQ.I.F IAQ Disc.In. Fan Config 0 to 2 IAQINFAN 0 40,84,85
AQ.CFOQ.A.C OAQ 4-20ma Sensor Config 0 to 2 OAQANCFG 0 45,84,85
AQ.SP AIR QUALITY SETPOINTS
AQ.SPIQ.O.P IAQ Econo Override Pos. 0 to 100 % IAQOVPOS 100 40,83-85
AQ.SPIQ.O.C IAQ Override Flow 0 to 31000 CFM IAQOVCFM 10000 85
AQ.SPDAQ.L Diff.Air Quality LoLimit 0 to 1000 DAQ_LOW 100 46,84-86
AQ.SPDAQ.H Diff.Air Quality HiLimit 100 to 2000 DAQ_HIGH 700 41,83-85
AQ.SPD.F.OF DAQ PPM Fan Off Setpoint 0 to 2000 DAQFNOFF 200 40,84,85
AQ.SPD.F.ON DAQ PPM Fan On Setpoint 0 to 2000 DAQFNON 400 40,84,85
AQ.SPIAQ.R Diff. AQ Responsiveness -5 to 5 IAQREACT 0 85
AQ.SPOAQ.L OAQ Lockout Value 0 to 2000 OAQLOCK 0 84,85
AQ.SPOAQ.U User determined OAQ 0 to 5000 OAQ_USER 400 41,85
AQ.SR AIR QUALITY SENSOR RANGE
AQ.SRIQ.R.L IAQ Low Reference 0 to 5000 IAQREFL 0 41,85
AQ.SRIQ.R.H IAQ High Reference 0 to 5000 IAQREFH 2000 41,85
AQ.SROQ.R.L OAQ Low Reference 0 to 5000 OAQREFL 0 85
AQ.SROQ.R.H OAQ High Reference 0 to 5000 OAQREFH 2000 85
IQ.PQ IAQ PRE-OCCUPIED PURGE
IQ.PQIQ.PQ IAQ Purge No/Yes IAQPURGE No 85
IQ.PQIQ.P.T IAQ Purge Duration 5 to 60 Minutes IAQPTIME 15 85
IQ.PQIQ.P.L IAQ Purge LoTemp Min Pos 0 to 100 % IAQPLTMP 10 85
IQ.PQIQ.P.H IAQ Purge HiTemp Min Pos 0 to 100 % IAQPHTMP 35 85
IQ.PQIQ.L.O IAQ Purge OAT Lockout 35 to 70 dF IAQPNTLO 50 85
HUMD HUMIDITY CONFIGURATION
HUMDHM.CF Humidifier Control Cfg. 0 to 4 HUMD_CFG 0 86,87
HUMDHM.SP Humidifier Setpoint 0 to 100 % HUSP 40 86,87
H.PID HUMIDIFIER PID CONFIGS
H.PIDHM.TM Humidifier PID Run Rate 10 to 120 Seconds HUMDRATE 30 86,87
H.PIDHM.P Humidifier Prop. Gain 0 to 5 HUMID_PG 1 86,87
H.PIDHM.I Humidifier Integral Gain 0 to 5 HUMID_IG 0.3 86,87
H.PIDHM.D Humidifier Deriv. Gain 0 to 5 HUMID_DG 0.3 86,87
ACT.C HUMIDIFIER ACTUATOR CFGS
ACT.CSN.1 Humd Serial Number 1 0 to 9999 HUMD_SN1 0 86,87
ACT.CSN.2 Humd Serial Number 2 0 to 6 HUMD_SN2 0 86,87
ACT.CSN.3 Humd Serial Number 3 0 to 9999 HUMD_SN3 0 86,87
ACT.CSN.4 Humd Serial Number 4 0 to 254 HUMD_SN4 0 86,87
ACT.CC.A.LM Humd Ctrl Angle Lo Limit 0 to 90 HUMDCALM 85 86,87
DEHU DEHUMIDIFICATION CONFIG.
DEHUD.SEL Dehumidification Config 0 to 5 DHSELECT 0 87,88
DEHUD.SEN Dehumidification Sensor 1 to 3 DHSENSOR 1 45,87,88
DEHUD.EC.D Econ disable in DH mode? No/Yes DHECDISA Yes 87,88
DEHUD.V.CF Vent Reheat Setpt Select 0 to 1 DHVHTCFG 0 87-89
DEHUD.V.RA Vent Reheat RAT offset 0 to 8 ^F DHVRAOFF 0 87-89
DEHUD.V.HT Vent Reheat Setpoint 55 to 95 dF DHVHT_SP 70 87-89
DEHUD.C.SP Dehumidify Cool Setpoint 40 to 55 dF DHCOOLSP 45 87-89
DEHUD.RH.S Dehumidify RH Setpoint 10 to 90 % DHRELHSP 55 87-89
DEHUH.SEL Heat Reclaim Config 0 to 2 RCLM_CFG 0 87-89
DEHUHZ.RT HumidiMizer Adjust Rate 5 to 120 Seconds HMZRRATE 30 88,89
DEHUHZ.PG HumidiMizer Prop. Gain 0 to 10 HMZR_PG 0.8 88,89
CNN CCN CONFIGURATION
CNNCNN.A CCN Address 1 to 239 CCNADD 1 91,92
CNNCNN.B CCN Bus Number 0 to 239 CCNBUS 0 91,92
CNNBAUD CCN Baud Rate 1 to 5 CCNBAUDD 3 91,92
BROD CCN BROADCST DEFINITIONS
BRODTM.DT CCN Time/Date Broadcast Off/On CCNBC On 91,92
BRODOAT.B CCN OAT Broadcast Off/On OATBC Off 91,92
BRODORH.B CCN OARH Broadcast Off/On OARHBC Off 91,92
BRODOAQ.B CCN OAQ Broadcast Off/On OAQBC Off 91,92
BRODGS.B Global Schedule Broadcst Off/On GSBC Off 91,92
BRODB.ACK CCN Broadcast Ack'er Off/On CCNBCACK Off 91,92
SC.OV CCN SCHEDULES-OVERRIDES
SC.OVSCH.N Schedule Number 0 to 99 SCHEDNUM 1 27,91,92
SC.OVHOL.T Accept Global Holidays? No/Yes HOLIDAYT No 91,92
SC.OVOTL Override Time Limit 0 to 4 Hours OTL 1 91,92
SC.OVOV.EX Override Time Limit 0 to 4 Hours OVR_EXT 0 91,92
SC.OVSPT.O SPT Override Enabled ? No/Yes SPT_OVER Yes 91,92
SC.OVT58.O T58 Override Enabled ? No/Yes T58_OVER Yes 91,92
SC.OVGL.OV Global Sched. Override ? No/Yes GLBLOVER No 91,92
ALLM ALERT LIMIT CONFIG.
ALLMSP.L.O SPT lo alert limit/occ -10 to 245 dF SPLO 60 91,92,123
ALLMSP.H.O SPT hi alert limit/occ -10 to 245 dF SPHO 85 91,92,123
ALLMSP.L.U SPT lo alert limit/unocc -10 to 245 dF SPLU 45 91,92,123
ALLMSP.H.U SPT hi alert limit/unocc -10 to 245 dF SPHU 100 91,92,123
ALLMSA.L.O EDT lo alert limit/occ -40 to 245 dF SALO 40 91,92,123
ALLMSA.H.O EDT hi alert limit/occ -40 to 245 dF SAHO 100 92,123
ALLMSA.L.U EDT lo alert limit/unocc -40 to 245 dF SALU 40 92,123
ALLMSA.H.U EDT hi alert limit/unocc -40 to 245 dF SAHU 100 92,123
ALLMRA.L.O RAT lo alert limit/occ -40 to 245 dF RALO 60 92,123
ALLMRA.H.O RAT hi alert limit/occ -40 to 245 dF RAHO 90 92,123
ALLMRA.L.U RAT lo alert limit/unocc -40 to 245 dF RALU 40 92,123
ALLMRA.H.U RAT hi alert limit/unocc -40 to 245 dF RAHU 100 92,123
ALLMOAT.L OAT low alert limit -40 to 245 dF OATL -40 92
ALLMOAT.H OAT high alert limit -40 to 245 dF OATH 150 92
ALLMR.RH.L RARH low alert limit 0 to 100 % RRHL 0 92
ALLMR.RH.H RARH high alert limit 0 to 100 % RRHH 100 92,124
ALLMO.RH.L OARH low alert limit 0 to 100 % ORHL 0 92,93,124
ALLMO.RH.H OARH high alert limit 0 to 100 % ORHH 100 92,93,124
ALLMSP.L SP low alert limit -0.5 to 5 "H20 SPL 0 92,93,124
ALLMSP.H SP high alert limit 0 to 5 "H20 SPH 2 92,93,124
ALLMBP.L BP low alert limit -0.25 to 0.25 "H20 BPL -0.25 92,93,124
ALLMBP.H BP high alert limit -0.5 to 0.5 "H20 BPH 0.25 92,93,124
ALLMIAQ.H IAQ high alert limit 0 to 5000 IAQH 1200 92,93,124