ZS pipe clamp-on temperature sensor
ZS Sensors Carrier Proprietary and Confidential CARRIER CORPORATION ©2017
Installation Guide All rights reserved
24
This sensor is primarily used to determine the fluid temperature in a pipe by reading the temperature of the pipe.
Pipe Clamp-on Temperature Sensor
Specifications for ZS pipe temperature sensor
Sensing element
Range:
Accuracy:
-40° to 212°F (-40° to 100°C)
±1.3°F (0.72°C)
Sensor Range:
Accuracy:
20° to 120°F (-5° to 50°C)
±0.9°F (0.5°C)
Enclosure material Polycarbonate, UL94V-0
Enclosure rating NEMA 4, IP66, UV rated
Enclosure dimensions Width:
Height:
Depth:
5 in. (12.7 cm)
4.15 in. (10.54 cm)
2.5 in. (6.35 cm)
Sensor pad 1.25" (3.18 cm) diameter copper
Power requirements 12 Vdc @ 6 mA
Power supply The 4-conductor Rnet cable from a controller supplies +12 Vdc @ 210 mA. For
additional power, use an external power supply. Use the above power requirements to
calculate the size of the external power supply. The controller and the external power
supply must share a common ground.
Communication 115 kbps
Mounting .5 in. (1.27 cm) stainless steel worm gear hose clamp
Listed by FCC Part 15-Subpart B-Class B, CE
ZS pipe clamp-on temperature sensor

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Carrier ZS2-C series and is the answer not in the manual?

Carrier ZS2-C series Specifications

General IconGeneral
BrandCarrier
ModelZS2-C series
CategoryTemperature Controller
LanguageEnglish

Related product manuals