24
• CEDIMA® • Technical Documentation • All rights reserved according to ISO 16016 • Changes serving technical progress reserved •
Maintenance and care
Joint cutter CF•22 E
Table 1 A: Repeated inspections of stationary electrical installations and equipment
Installation / Equipment Control period Type of control Inspector
electrical installations and
stationary equipment
4 years checking for good
operational condition
electrical specialist
electrical installations and
stationary electrical equipment
in “operating sites, rooms and
installations of special kind”
(DIN VDE 0100 Group 700)
1 year checking for good
operational condition
electrical specialist
protective measures with residual-
current-operated protective
devices in non-stationary
installations
1 month eectivity electrical specialist or
electro-technical trained
person, using suitable
measuring and control
instruments
Fault current, residual current
device and circuit breaker
– in stationary installations
– in non-stationary installations
6 months
every working day
checking for faultless
function by releasing the
checking device
operator
Table 1 B: Repeated inspections of non-stationary electrical installations and equipment
Installation / Equipment Control period
standard values and maximal
values
Type of control Inspector
– non-stationary electrical
equipment (if used)
– extension cables and
connecting cables with sockets
or plugs
– connection cables with plugs
– mobile cables with plugs and
sockets
as a standard value every
6months, on building sites
3 months*).
Obtaining a margin of error
< 2 %, the control period can be
extended.
Maximum values:
On building sites, in production
facilities and work shops or
under similar conditions, one year
in oces or under similar
conditions, two years.
checking for
good operational
condition
electrical specialist, when
using appropriate measuring
instruments also electro-
technically trained persons
For more concrete specications, refer to “rules for safety and health protection - selection and operation of electrical
installations and operating equipment on building sites“ (BGI 608).
5.6 Safety checks of the electrical system according to DGUV regulation 3 § 5,
processing instruction paragraph 1 No. 2