EasyManua.ls Logo

Central Boiler FireStar - Burn Adjustment Guide; Excessive Smoke Condition; Fire Goes Out Condition

Central Boiler FireStar
20 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
FORGE OUTDOOR COAL FURNACE • OWNER'S MANUAL
Burn Adjustment Guide
Use the following recommendations to help obtain a clean and ecient burn
and extract the most heat from your coal. When making any adjustments, it
is best to change settings gradually and allow the furnace to burn for a few
loading cycles to determine if the settings you've changed are benecial to
operation.
CONDITION: Excessive smoke from the chimney.
NOTE: This condition is typically only an issue when burning bituminous.
RECOMMENDED ACTIONS:
Make sure you are using IGNITION ASSIST MODE after lling the furnace
with a new load of bituminous coal and closing the rebox door.
Increase time of IGNITION ASSIST DURATION (Menu #6) to increase
the amount of time air is available.
Increase IGNITION ASSIST OVER AIR SETTING (Menu #8), if not
already set to 100. Also make sure that the ue gas temperature doesnt
consistently drop after making this adjustment. If it does, the smoke could be
getting diluted instead of burned.
Decrease the IGNITION ASSIST UNDER AIR SETTING (Menu #7) to
reduce the under air and slow down the rate that volatiles are released from
the coal.
Try dierent loading techniques making sure that there is an area of exposed
glowing coals to ignite the volatile gases.
Check to make sure that neither the over or under air outlets are plugged.
Make sure the outdoor furnace is up to temperature and that the heat load is
not greater than the outdoor furnace heat output capacity.
Some types of coal, because of their sulfur and impurity content, will always
smoke, regardless of what settings are adjusted.
CONDITION: Fire goes out.
RECOMMENDED ACTIONS:
Make sure there are enough glowing coals to ignite the fuel load. If not, load
more frequently so there are enough coals remaining to ignite the fuel load.
Make sure there are no restrictions to the combustion air. Check for any
clinker buildups in the rebox, check the over and under air holes to ensure
they are free of debris, and make sure the combustion fan inlet isnt blocked.
Make sure the over and under air actuators, and the combustion blower are
functioning properly.
Increase the STANDARD RUN MODE UNDER AIR SETTING (Menu
#10) to provide additional under air (primary combustion air).

Related product manuals