-11-
4.6 Communication Cable
If needed, the network cable should be made like the diagram shown above. But the
network cable between the battery and Inverter should be made following the definition
of Inverter. If available, use a LAN cable tester to check whether the cable is faulty.
4.7 Storage
If the battery is not to be installed immediately, or removed from operation and needs
to be stored for a long period, please choose an appropriate location to store it.
Instructions for storage are:
Do not stack more than 8 battery boxes.
The temperature of the battery stored recommended in the range of -20°C to 25°C.
Do not expose to water
The ESS box should be upright and not stacked upside down when storing the ESS
box.
If the ESS needs to be stored for over 3 months, the DC circuit of the battery should
be disconnected. Otherwise, the battery would discharge at a minimum rate and
capacity degrades depending on storage time, the battery self-consumption less than
5w. And, if the battery is stored for over 6 months, it is suggested to connect the battery
with the inverter and commission the system.
5 Battery Installation
5.1 Package Items
These items are included in the package: