What to do if CG Emotron VFX48 Controller displays 'Over curr F'?
- MMichael BurtonAug 21, 2025
If the CG Controller displays 'Over curr F', it means the motor current exceeds the peak AC drive current. This can be due to several reasons: * Too short acceleration time. * Too high motor load. * Excessive load change. * Soft short-circuit between phases or phase to earth. * Poor or loose motor cable connections. * Too high IxR Compensation level. To resolve this, check the acceleration time settings (increase if needed), motor load, cable connections, and for moisture in the motor. Also, lower the level of IxR Compensation [352].