EasyManua.ls Logo

Chentronics iScan3 Series - Remote File Select

Chentronics iScan3 Series
25 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MNL-ISCAN3, REVB INSTALLATION & OPERATION MANUAL Page 21 of 25
DCO #12743 For Technical Support Call: +1.866.821.5504 Schedule Document
Remote File Select
The Remote File Select feature provides a means for automatically selecting one the configuration files resident within the
scanner. iScan3 has a two wire or four wire option to remotely select files. File select configurations are wire fault protected;
[A5]
meaning if any wire combination is broken, i.e. loose wire connection or a wire gets cut, the scanner will fault. Switching
must occur in less thatn 800ms. Per NFPA, file selects should not be used to “blind” scanner from seeing flame, to obtain a
start permissive.
FOUR WIRE CONFIGURATION: USES TWO RELAYS
File Select
SEL 3
SEL 2
SEL 1
SEL 0
A
N.O. CLOSED to C
OPEN
N.O. CLOSED to C
OPEN
B
OPEN
N.C. CLOSED to C
N.O. CLOSED to C
OPEN
C
OPEN
N.C. CLOSED to C
OPEN
N.C. CLOSED to C
D
N.O. CLOSED to C
OPEN
OPEN
N.C. CLOSED to C
TWO WIRE CONFIGURATION: USES ONE RELAY
File Select
SEL 1
SEL 0
B
N.O. CLOSED to C
OPEN
C
OPEN
N.C. CLOSED to C
Note: Connect iScan3 SEL (File Select) wires via dry relays contacts (supplied by others) per above. Connect the common (C)
side of the File Select relays to -24 VDC return. Remote File Select must be enabled otherwise SEL inputs are ignored. Refer to
Remote File Select (RFS) section of MNL-iSCAN for instructions on setting up and using the Remote File Select feature