EasyManua.ls Logo

Chentronics iScan3 Series - Wiring Instructions; Wiring Diagram; Wiring Notes

Chentronics iScan3 Series
25 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MNL-ISCAN3, REVB INSTALLATION & OPERATION MANUAL Page 13 of 25
DCO #12743 For Technical Support Call: +1.866.821.5504 Schedule Document
Wiring Instructions
All wiring shall be done in accordance with all applicable local and national codes, standards, and ordinances. The
scanner has a quick connect cable. This cable does not require a flexible conduit if permitted by local authority.
Connections for power, Earth Ground, and Flame Relay (N.O. and Common) are required for all applications. Use of
the 4-20 mA outputs, Communications, and connections are “as-required” for each application.
Wiring Diagram
Wiring Notes
Note 1 If more than one 24 VDC supply is required, the 24 VDC returns labeled as “DC (-)” shall be connected to each
other.
Note 2 If more than one 24 VDC supply is required, the 24 VDC source connections labeled as “DC (+)” shall be
isolated from all other power supplies. If switching power supplies are used the supplies may be connected via a
wired OR diode configuration. NOTE: the BLOCKING DIODE must be rated for a minimum of 50 volts and 10 Amps.
Note 3 The 24 VDC return, “DC (-)”, shall be used as the low side of the File Select relays.
Note 4 The 24 VDC return, “DC (-)”, is the return for the 4–20 mA output loop(s). Input must be isolated type.
Maximum current loop resistance is 750 ohms.