EasyManuals Logo

Chigo CCB-18HR1 User Manual

Chigo CCB-18HR1
166 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #150 background imageLoading...
Page #150 background image
R410A50Hz Universal Outdoor Series Technical Manual Installation
147
GD Chigo Heating & Ventilation Equipment Co., Ltd.
②. Special vacuum dry procedure
This vacuum dry method is used in the following conditions:
There’s moisture when flushing the refrigerant pipe.
Rainwater may enter into the pipe.
Vacuum dry for the first time ······ 2h pumping
③. Vacuum destroy for the second time ······ Fill nitrogen to 0.5Kgf/cm
2
Because nitrogen is for drying gas, it has vacuum drying effect during vacuum destroy. But if the
moisture is too much, this method can’t dry thoroughly. So, please pay more attention to prevent
water entering and forming condensation water.
. Vacuum dry for the second tim·····1h pumping
Determinant: Pass if achieving below -755mmHg. If -755mmHg can’t be achieved in 2h, repeat
procedure and .
. Vacuum placing test ······ 1h
. Sketch map of special vacuum dry procedure

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Chigo CCB-18HR1 and is the answer not in the manual?

Chigo CCB-18HR1 Specifications

General IconGeneral
BrandChigo
ModelCCB-18HR1
CategoryAir Conditioner
LanguageEnglish

Related product manuals