R410A50Hz Universal Outdoor Series Technical Manual Duct Type Indoor Unit
82
GD Chigo Heating & Ventilation Equipment Co., Ltd.
11.The Specification of Wiring
Type
CTA-18HR1
CTA-24HR1
CTB-18HR1
CTB-24HR1
CTB-36HR1
CTB-48HR1
Power
Phase
1-phase
1-phase
1-phase
1-phase
1-phase
1-phase
Frequency and
Voltage
220-240V, 50Hz
Indoor Unit Power Wiring
(mm
2
)
2.5mm
2
1.0mm
2
2.5mm
2
1.0mm
2
1.0mm
2
1.0mm
2
Indoor/Outdoor
Connecting
Wiring (mm
2
)
Ground
Wiring
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
Strong
Electric
Signal
0.75mm
2
0.75mm
2
0.75mm
2
0.75mm
2
0.75mm
2
0.75mm
2
Type
CTB-60HR1
CTB-48HR1-B
CTB-60HR1-B
CTH-48HR1
CTH-60HR1
Power
Phase
1-phase
1-phase
1-phase
1-phase
1-phase
Frequency and
Voltage
220-240V, 50Hz
Indoor Unit Power Wiring
(mm
2
)
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
Indoor/Outdoor
Connecting
Wiring (mm
2
)
Ground
Wiring
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
1.0mm
2
Strong
Electric
Signal
0.75mm
2
0.75mm
2
0.75mm
2
0.75mm
2
0.75mm
2