Number of poles
Protection function
Model
Rated current In (A)
Installation mode
Intelligent Controller
Standard
(Default
configuration)
M type
Communication
type
(Optional
configuration)
3H-type
Notes:
Protection
function
Settable
range and
conventional
factory tuning
Controller power
Auxiliary functions
Optional function
1. Ammeter
function
2. Self-diagnostic
function
3. Tuning function
4. Test function
5 Display function
Frequency display
Power Factor show
Active power display
Load monitoring
function
Note: For the specific
optional function, refer
to List of controller
functions in the sample
(The cost of optional
functions will be
calculated additionally).
Voltage display
Drawout type
Fixed type (Note: no fixed type when In> 4000A)
Three poles Four poles
NA1-2000X NA1-2000XN NA1-2000XH NA1-3200X NA1-3200XN
NA1-4000X
1250 1600 2000
630 800 1000
3200
2000 2500
NA1-1000X
800 1000
200 400 630
4000
6300(no four poles)
4000 5000
Undervoltage
release (default
configuration)
Shunt release
Electric motor
Interlock device
(surcharge)
Accessories
(surcharge)
Electrical accessories
Special requirements
The main circuit
connection
NA1-1000X~6300X Ordering specification
Closing electromagnet
Note: The casing current, rated current and auxiliary control voltage must be specified when ordering!
2
Tel.:0577-62877777-6213 Fax :0577-62877777-6288
Note: 1) Please mark “√” or fill figure in the relative ” ” if no mark, we will provide according to conventional.
Note: ) The operational fuction of the intellgent controller and special requirements require additional costs.
1. Ir overload long delay, Isd short-circuit short delay inverse
time + definite time, Ii transient short-circuit, Ig single-phase
grounding 4-section protection
2. Ir overload long delay, Isd definite time short-circuit short
delay,Ii transient short-circuit, Ig single-phase grounding 4-section
protection
1. Ir overload long delay short-circuit short delay inverse time
+definite time Ii transient short-circuit, Ig single-phase grounding
4-section protection
2. Ir overload long delay, Isd definite time short-circuit short delay,
Ii transient short-circuit, Ig single-phase grounding 4-section protection
3. with PROFIBUS-DP communication protocol
with MODBUS communication protocol
Isd
1. Ir overload long delay, short-circuit short delay inverse
time + definite time, Ii transient short-circuit, Ig single-phase
grounding 4-section protection
2. Ir overload long delay, Isd definite time short-circuit short
delay,Ii transient short-circuit, Ig single-phase grounding 4-section
protection
Isd
Multifunctional
(Optional
configuration)
3M type
Customer: Tel: Date:
Quantity:
NA1-6300X
NA1-4000X NA1-3200X NA1-2000X NA1-1000X
Ir long delay current setting range: (0.4 to 1) In
Overload 1.5Ir action time setting range: 15,30,60 ...... 480s
Ii instantaneous current setting range: 1.5In ~ 50kA/65kA/75kA
! Conventional factory tuning: 12In [Note: 3M, 3H for (1.5In~50kA/65kA/75kA)]
Ig earthing protection current setting range: (0.2 to 0.8) In; the earthing protection time setting range: (0.1to0.4)s
! Conventional factory setting: 0.5 In; OFF
AC380V,AC400V,AC220V,AC230V,AC127V,DC220V,DC110V
AC380V,AC400V,AC220V,AC230V,AC127V,Order_____V ,Non-undervoltage
Instantaneous delay, s; Resistance capacity loss release delay (1,3,5) s, and optional non-adjustable
AC380V,AC400V,AC220V,AC230V,AC127V,DC220V,DC110V
Mechanical linkage: Link interlock Cable interlock
Door interlock: Switch body position door interlock Switch on/off state door interlock (drawer-type)
Button lock: Panel products on/off button lock
Key lock: 1 lock 1 key 2 locks 1 key 3 locks 1 key 3 locks 2 keys 5 locks 3 keys pecial custom__lock__ key S
External transformer: External N phase transformer [(3P+N)T type
External leakage zero sequence current transformer (E mode) External ground current transformer (W)
Module: RU-1 relay module PSU-1 Power module ST-DP protocol converting module
Position signaling devices ( Test ) Connected Unconnected Mechanical counting device
Horizontal Vertical connection (with L vertical bus-bar) connection (default)
horizontalRotation busbar connection (Drawer In ≤ 3200)
Rotation busbar vertical connection (drawer-type In ≤ 3200)
! Conventional factory setting: short delay current 8Ir ;
! Conventional factory tuning: Short delay action time 0.4s
[Note: 3M, 3H for (1.5 to 15) Ir]
(Optional)
I short delay current setting range: (1.5 to 15) Ir;
short delay action time (0.1 ~ 0.4) s
sd
AC380V,AC400V,AC220V,AC230V,AC127V,DC220V,DC110V
AC380V,AC400V,AC220V,AC230V,AC127V,DC220V,DC110V
! Conventional factory tuning: overload 1.5Ir; action 15s
! Conventional factory tuning: overload long delay 1.0In
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
(Optional)
NA1-6300X NA1-6300XN
4. NA1-1000X operational configuration (additional costs)
Under voltage delayed release; wire-cable mechanical
interlock;
key lock; External current transformer earthing protection;
Vertical busbar; 6 groups changeover contacts;
H type intelligent controller; Phases barrier, position signal.
3. NA1-2000X~6300X operational configuration (additional costs)
Nonadjustable under voltage delayed release (1s, 3s, 5s);
Connecting-rod type mechanical interlock (for drawout type);
Wire-cable mechanical interlock; Button lock; Key lock;
Door interlock'Locking device;
External current transformer earthing protection; Vertical
busbar;
Rotating busbar (IN≤3200);
3NO (normal open) and 3NC (normal close) contacts;
4NO and 4NC contacts; 5 groups changeover contacts;
3 groups changeover contacts; H type intelligent controller;
Position signal; Counter; Protecting cover (NA1-2000);
Double power controller.
2. NA1-1000X fundamental configurations
a. Motor-driven:
Under-voltage instantaneous release;
Shunt release;
Closing electromagnet;
Motor driven operating mechanism;
4 normal open and 4 normal close auxiliary
contacts;
M-type Intelligent Controller;
Closing and breaking push button lock;
Horizontal wiring of main circuit;
Doorcase;
Element of main circuit;
Operating instructions of Air Circuit Breaker;
Packing box;
Drawer seat(Drawout type)
1. NA1-2000X~6300X fundamental configurations
a. Motor-driven:
Under-voltage instantaneous release;
Shunt release;
Closing electromagnet;
4 suits of transform contact;
Motor driven operating mechanism;
M-type Intelligent Controller;
Horizontal wiring of main circuit;
Doorcase;
Element of main circuit;
Operating instructions of M-type Intelligent Controller
Operating instructions of Air Circuit Breaker;
Packing box;
Drawer seat (Drawout type)
Configuration instructions
C
NA1
Air Circuit Breaker
P-104
P-103
NA1
Air Circuit Breaker
b. Manual:
Under-voltage instantaneous release;
4 suits of transform contact;
M-type Intelligent Controller;
Horizontal wiring of main circuit;
Doorcase;
Element of main circuit;
Operating instructions of M-type Intelligent
Controller
Operating instructions of Air Circuit Breaker;
Packing box;
Drawer seat(Drawout type)
b. Manual:
Under-voltage instantaneous release;
4 normal open and 4 normal close auxiliary
contacts;
M-type Intelligent Controller;
Horizontal wiring of main circuit;
Closing and breaking push button lock;
Doorcase;
Element of main circuit;
Operating instructions of Air Circuit Breaker;
Packing box;
Drawer seat(Drawout type)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the CHINT NA1-2000X and is the answer not in the manual?

CHINT NA1-2000X Specifications

General IconGeneral
BrandCHINT
ModelNA1-2000X
CategoryCircuit breakers
LanguageEnglish

Related product manuals