NVF5 Series User Manual        Chapter 8 Maintenance 
5.  Check whether the DC Bus filter capacitors discolor, Peculiar smell, bubbling, 
leakage, etc. 
8.3 Routine Maintenance 
The inverter must run in the standard environment. If some unexpected situations 
occur during operation, the user should follow the instructions in the table below to do 
routine maintenance job. The good method to extend the life of the inverter is to maintain a 
good running environment, record the daily operation data, and detect the exception as 
early as possible.   
Table 8.1 Routine Maintenance Table 
Criteria 
Enviroment 
1
.
Temperature, 
humidity 
Any 
time 
1
.
Thermometer, 
1
.(
-10
~+
45
)
℃
,
(
45
~
50
)
℃
dreating 
2
.
Dust, water 
2
.
Visual 
2
.
No water leakage 
3
.
Gas  3
.
Smell  3
.
No bad smell 
Inverter 
1
.
Vibration,Heat 
Any 
time 
1
.
Enclosure 
Touch 
1
.
Stable 
vibration,reasonable 
2
.
Noise  2
.
Auditory sense  2
.
No abnormal sound 
Motor 
1
.
Heat 
Any 
time 
1
.
Hand Touch  1
.
No abnormal heat 
2
.
Noise  2
.
Auditory 
2
.
Uniform noise 
Status   
1
.
Output Current 
Any 
time 
1
.
Ammeter 
1
.
Within the range of 
ratings 
2
.
Output Voltage  2
.
Voltmeter 
2
.
Within the range of 
ratings 
3
.
Internal 
3
.
Thermometer 
3
.
Temperature Rise 
less than 35 K 
8.4 Regular Maintenance 
According to the using environment, the user can conduct a regular inspection for the 
inverter every three months or six months.。 
General inspection contents: 
1.Whether screws of the I/O terminal are loose, tighten with a screwdriver; 
- 98 -