NVF5 Series User Manual       Chapter 7 Troubleshooting 
Chapter 7 Troubleshooting 
7.1 Diagnostic   
7.1.1 Diagnostic process 
The flow chart of the fault diagnosis is shown below 
YES
NO
If serious failure appears after 
power up, such as no display, 
abnormal sound etc.
End
Check Fault code refer to 
chapter 7.
2. Can solve or not?
Check abnormal handing 
refer to chapter 7.3. Can 
solve or not?
Fault reset
Asking for Chint 
technical support
YES
Power off 
immediately
NO
NO
Start
 
Figure 7-1-1 Fault Diagnosis Flow Chart 
7.1.2 Fault description and Trouble shooting 
If a fault appreas,Please see for an explanation of the fault code and check by 
youself firstly before asking for help from Chint or Chint channels.When you need 
support,please contact Chint or Chint channels. 
E.OC1 
Inverter 
Accel. 
running 
overcurrent 
1、  Low grid voltage 
Check the input power 
supply 
2、Directly and quickly start 
Start inverter when motor 
stop 
3、Accel. Time too short 
Increase accel. time 
4、Incorrect Motor Nameplate 
Motor auto tuning 
5、Too small inverter power 
  Enlarge inverter power 
rate 