NVF5 Series User Manual     Chapter 6 Parameter Function Description 
F8.33 
0.0min 
(0.0  ~  6500.0)min 
- 
6.20 Start At Power Up 
Enable/disable inverter automatically start on power up with different Start 
Commands and the Auto Restart delay time. 
Code  Name  Default  Setting Range  Description 
F8.35 
Function 
0 
0  ~  1 
0:Ineffective 
1:Effective 
F8.36 
0.0s 
(  0.0  ~  10.0)s 
- 
6.21 Sleep Wake Mode 
Sleep function is mainly used in pump water supply, air supply control fields requiring 
automatic sleep,this function can make inverter output 0 Hz when reaching user setting 
preset sleep leve which realize energy saving. Sleep function needs to be combined with 
PID function.See process diagram 6-9-6. 
If the sleep function is switched on  (F8.37 set to 1,F9.28(Close loop run mode)
set to 1(run when stop)), and the system is in running mode,When the output frequency 
is detected less than or equal to the sleep frequency(F8.38)  and the duration reaches the 
sleep delay time(F8.39), inverter enters the sleep mode automatically(Inverter run in0Hz);
When PID feedback(Fd .29)is less than PID reference(Fd .28),and the deviation is more 
than wake leve(F8.40), and the duration reaches the wake delay time(F8.41),inverter 
enters the wake mode automatically,and the system leave sleep mode automatically and 
inverter run again. 
Sleeping
Freq.
Hz
t
Setting 
Freq.
Ref.-Wake
offset
Feedback
Ref.
t
0
Sleeping 
delay
Wake 
delay
 
Figure 6-21-1 Sleep and Wake