NVF5 Series User Manual  Chapter 6 Parameter Function Description 
In this mode,DI3 is Run Enable input terminal,after Running command is given by 
DI1,DI2 control the direction.As shown in the below figure,when SB1 is closed,when 
pressing SB2 the inverter will start,when K is opened the inverter will run forward,when K 
is closed the inverter will run reverse;when SB1 is opened the inverter will stop. In normal 
Start and Running process,SB1 must be kept closed,SB2 will be took effect in rising 
edge.   
+24V
PLC
DI1
DI3
COM
SB2
DI2
SB1
K
K RUN
0
1
Run 
Forward
Run
Reverse
Figure 6-1-4 Three Wire Control Mode2 
Paremeters Setting as below: 
Command Channel 
Selection 
Terminal Control 
Mode Selection 
Three Wire Control Mode 2 
Forward(“Enable”) 
Selection 
Reverse(“FWD/REV 
Switch”) 
 
6.1.3 “Comm.”Setting Control 
 Set parameter F0.01=2,can realize Start、Stop command by Comm. control 
NVF5  supports  Modbus  Communication mode.  See Appendix A about Modbus 
protocol description. 
6.1.4 “Remote Keypad”Setting 
Set parameter F0.01=3,when remote keypad is used,the inverter can be realized 
RUN、STOP  by remote keypad.When pressing RUN  key,the inverter will start,RUN 
indicator light;In running mode,press STOP key    the inverter will stop,RUN indicator 
light off. 
- 41 -