NVF5 Series User Manual     Chapter 6 Parameter Function Description 
Running freq.
Time
Freq.
Deceleration time
Stop 
command
 
Figure 6-3-4 Ramp Decel. Stop Time Sequence Chart 
 Coast Stop 
Set parameter F1.05=1,inverter coast stop. When the stop command is effective,the 
inverter immediately stops output and the motor will execute coast stop. 
Time
Freq.
Coast stop by load inertial
Stop 
command
 
Figure 6-3-5 Coast Stop Time Sequence Chart 
  Ramp Stop+DC Injection Braking Stop 
Set parameter F1.05=2,  inverter ramp stop,after the frequency drops to the DC 
braking starting frequency of parameter F1.06, the inverter starts DC braking.   
Freq. 
Hz
Time t
Output Vol.
(RMS value)
RUN 
command
DC braking 
starting Freq.
DC brake 
waiting time
DC brake 
level
DC brake 
time
 
Figure 6-3-6 Ramp Stop+DC Injection Braking Stop Time Sequence Chart 
- 60 -