NVF5 Series User Manual     Chapter 6 Parameter Function Description 
F4.02 
Torque Boost 
Cut-off Point 
50.00Hz 
0.00Hz  ~F0.07 
- 
F4.03 
Multi-point VF 
Frequency Point 3 
0.00Hz 
F4.05  ~  F2.04 
-   
F4.04 
Multi-point  VF 
Voltage Point 3 
0.0% 
(0.0 ~ 100.0)% 
- 
F4.05 
Multi-point VF 
Frequency Point 2 
0.00Hz 
F4.07  ~  F4.03 
- 
F4.06 
Multi-point  VF 
Voltage Point 2 
0.0% 
(0.0 ~ 100.0)% 
- 
F4.07 
Multi-point VF 
Frequency Point 1 
0.00Hz 
0.00 Hz~F4.05 
- 
F4.08 
Multi-point  VF 
Voltage Point 1 
0.0% 
(0.0 ~ 100.0)% 
- 
● General Constant Torque V/F curve:Under the rated frequency, the output voltage 
changes linearly with the output frequency, which is suitable for general mechanical 
machines such as large inertia fans, punches, centrifuges, pumps and so on. 
Output Vol. V
Output freq.  f
Torque boost
Torque boost 
cut-off freq.
Max. 
Output Vol.
Normal 
Running Freq.
 
Figure 6-5-1 General Constant Torque Linear V/F Curve 
● Custom Multi-Point V/F Curve:range of frequency setting    0.00Hz  ~Motor Rated 
Frequency,range of voltage setting    0.0%  ~  100% Corresponding 0V  ~Motor Rated 
Voltage , the setting of Multi-Point  V/F curve is normally decided by the load 
characteristics of the motor. 
- 65 -