EN - 27
Pairing the sensor
Once the sensor has been stimulated, use the control terminal to select the CONFIRM value in the setting field:
- The sensor search sequence is activated
- The search time is 30 seconds maximum: monitor the progress bar displayed on the screen. The progress bar moves forward
one step every 3 seconds.
5 search results are possible:
Case 1
The outdoor sensor has not been found:
- Repeat the sensor stimulation procedure
- Press the button
- Restart the sensor pairing sequence
Case 2
The outdoor sensor has been found and pairing has been successful:
- Updating of the outdoor temperature value at the top of the terminal unit screen
(3 lines --- disappear)
- Press the button to end the sequence
Case 3
The sensor has been found but its characteristics are incorrect (old version of the
sensor or sensor incompatible):
- Replace the outdoor sensor with a compatible version
- Activate the stimulation procedure for the new sensor
- Press the button
- Restart the sensor pairing sequence
Case 4
The sensor has been found, but pairing failed:
- Repeat the sensor stimulation procedure
- Press the button
- Restart the sensor pairing sequence
Case 5
Several sensors have been found:
- Make sure you only activate the stimulation procedure on one sensor
- Press the button
- Restart the sensor pairing sequence
Outdoor sensor pairing