A roof-mounted fan tray and an air-cooling scheme in which the fan tray pulls air in at the bottom of the
cabinet and sends it out from the top, with a minimum airflow of 849.5 m
3
/h exiting the cabinet roof
through the fan tray, to be available.
Nonperforated (solid and sealed) front and back doors and side panels to be present so that air travels
predictably from bottom to top.
The overall cabinet depth to be 36 to 42 in. (91.4 to 106.7 cm) to allow the doors to close and to facilitate
adequate airflow.
A minimum of 150 sq. in. (968 sq. cm) of open area to be available at the floor air intake of the cabinet.
The lowest piece of equipment to be installed at a minimum of 1 RU (1.75 in. or 4.4 cm) above the floor
openings to prevent blockage of the floor intake.