Power Supply Requirements Specifications
The following table provides a sample calculation of power for the Cisco MDS 9396T switch AC power
supply.
Table 3: Power Dissipation for AC Power Supply
Power at
220V/50HZ
(Watts)
Power at
110V/60HZ
(Watts)
Fan
Trays
LEMOptics
Number
Optics
Speed
VoltageTemperatureTraffic
Rate
PSUPower
Mode
330338204832G-SWNominal25°C50%2Typical
555570396
595610239632G-SWNominal
25°C100%2Max
61862732G-LW
65567332G-SW
756
79832G-LW55°C
806858Nominal
+ 5%
To prevent a loss of input power, ensure that the total maximum load on each circuit supplying the power
supply is within the current ratings of the wiring and breakers.
Note
Connection Guidelines for AC-Powered Systems
For connecting the Cisco MDS 9396T switch AC power supplies to the site power source, follow these basic
guidelines:
• Each power supply should have its own dedicated branch circuit.
• For international, circuits should be sized according to local and national codes.
• The AC power receptacles used to plug in the chassis must be the grounding type. The grounding
conductors that connect to the receptacles should connect to protective earth ground at the service
equipment.
Cisco MDS 9396T Multilayer Fabric Switch Hardware Installation Guide
51
Technical Specifications
Power Supply Requirements Specifications