Make sure that the switch rack-mount kit includes the following parts:
Front rack-mount brackets (2)
Rear rack-mount brackets (2)
Slider rails (2)
M4 x 0.7 x 8-mm Phillips pan-head screws (10)
The rack is installed and secured to its location.
Step 1 Install two front rack-mount brackets and the two rear rack-mount brackets to the switch as follows:
a) Determine which end of the chassis is to be located in the cold aisle as follows:
If the switch has port-side intake modules (fan modules with burgundy coloring), position the switch so that its
ports will be in the cold aisle.
If the switch has port-side exhaust modules (fan modules with blue coloring), position the switch so that its fan
and power supply modules will be in the cold aisle.
b) Position the front rack-mount bracket and the rear rack-mount bracket so that its screw holes are aligned to the screw
holes on the side of the chassis.
You can align the holes in the rack-mount bracket to the holes on the side of the chassis (see the two
ways to mount these brackets on a typical chassis, in following figure). The holes that you use depend
on the requirements of your rack and the amount of clearance required for interface cables (3 inches [7.6
mm] minimum) and module handles (1 inch [2.5 mm] minimum).
Note
Cisco Nexus 9332D-GX2B ACI-Mode Switch Hardware Installation Guide
17
Installing the Chassis
Installing the Switch Using the NXK-ACC-KIT-1RU Rack-Mount Kit