Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)
The airflow sleeve (N9K-AIRFLOW-SLV) is installed to allow proper airflow, so that the switch is properly
cooled. This airflow sleeve is only compatible with rack mount kit (N3K-C3064-ACC-KIT).
Table 1: Airflow Sleeve (N9K-AIRFLOW-SLV) Minimum and Maximum Rack Rail Depth.
Maximum Rack DepthMinimum Rack DepthChassis
748.25 mm636.49 mmN9K-C92348GC-X
916.60 mm824.80 mmN9K-C9316D-GX
898.70 mm794.20 mmN9K-C9332C
915.80 mm824.00 mmN9K-C9332D-GX2B
903.98 mm802.39 mmN9K-C9336C-FX2
898.70 mm806.90 mmN9K-C9336C-FX2-E
764.29 mm672.49 mmN9K-C9348GC-FXP
873.09 mm781.29 mmN9K-C93108TC-FX
769.69 mm672.49 mmN9K-C93108TC-FX3P
873.09 mm781.29 mmN9K-C93180YC-FX
784.25 mm672.49 mmN9K-C93180YC-FX3
784.25 mm672.49 mmN9K-C93180YC-FX3S
916.60 mm824.80 mmN9K-C93600CD-GX
You supply the screws to mount the airflow sleeve.
Note
Before you begin
Verify that your shipment is complete.
Install your rack in a secure location.
Insert the airflow sleeve into the rack and attach it as follows:
a) Holding the airflow sleeve (N9K-AIRFLOW-SLV) with both hands, position it in front of the fan side of the chassis.
b) Holding the airflow sleeve level, insert screws (12-24 or 10-32, depending on the rack type) in each of the two front
rack-mount flanges (using a total of two screws) and into the cage nuts or threaded holes in the vertical rack-mounting
rails (see the following figure).
Cisco Nexus 9332D-GX2B ACI-Mode Switch Hardware Installation Guide
20
Installing the Chassis
Installing the Airflow Sleeve (N9K-AIRFLOW-SLV)