Some power supplies might have UL listed capabilities that are greater than the maximum power requirements
for a switch. To determine the power consumption characteristics for the switch, use the typical and maximum
requirements listed in the following table.
Note
Heat Dissipation
Requirement
Maximum Power
Consumption (AC or DC)
Typical Power
Consumption (AC or DC)
Switch
2651.234 BTUs per hour777 W484 WCisco Nexus 9336C-FX2
Power Specifications
Power specifications include the specifications for each type of power supply module.
1100-W AC Power Supply Specifications
These specifications apply to the following power supplies:
• NXA-PAC-1100W-PE
• NXA-PAC-1100W-PI
SpecificationCharacteristic
Nominal range: 100 and 240 VAC (Range: 90-132
VAC, 180-264 VAC)
AC input voltage
Nominal range: 50 to 60 Hz (Range: 47-63 Hz)AC input frequency
12 A at 115 VAC
6 A at 240 VAC
Maximum AC input current
760 A at 100 VACMaximum input volt-amperes
1100 WMaximum output power per power supply
33 A (sub-cycle duration)Maximum inrush current
12 ms at 1100 WMaximum hold-up time
12 VDCPower supply output voltage
12 VDCPower supply standby voltage
Climate Savers Platinum Efficiency (80Plus Platinum
certified)
Efficiency rating
RSP1Form factor
Cisco Nexus 9336C-FX2 NX-OS Mode Switch Hardware Installation Guide
41
System Specifications
Power Specifications