SIMPWS1 REV3 13/07/11 PAGE 18 OF27
11.1.2 WS1 100-350 L
PARAMETER UNITS 100L 120L 150L 250L 350L
MAX.SERVICE
FLOW
M3/hr 4 4.3 6 6 6
SYSTEM CAPACITY Kg
CaCO3
5 6 7.5 12.5 17.5
CAPACITY @
300PPM
M3 16.7 20 25 41.75 58.45
SALT USED PER
REGEN
Kg 14 16.8 21 35 49
REGENERATION
TIME
MIN 96 96 96 120 140
SALT STORAGE
CAPACITY
Kg 160 160 300 400 500
MAX OPERATING
TEMP
O
C 50 50 50 50 50
MAX FLOW TO
DRAIN
LIT/MIN 19 19 26 37 57
IMPORTANT NOTES
Much of the data quoted in the above table is affected by the inlet pressure,
and so should be regarded as nominal only.
Total flow to drain will be similarly affected and is therefore not quoted, but
will be about 6 times the resin volume.