6.5. Use of 12VDC Output
For 12VDC equipment connected to the 12VDC out no fuse is needed, as this is included in the LPS.
Figure 8
6.6. Anderson connector assembly (12VDC In/Out)
When installing the unit, make sure to use 16mm
2
cables for the DC connections.
Figure 9
Step 1: Use 16 mm
2
cable. Maximum length 5m. Strip 14 mm.
Figure 10
Step 2: Insert cable in contact and crimp with tool.
Step 3: Insert contact in housing, push until click.