Tranquility
®
16
COMPACT (TC) Series
MODELS TCH/V 006 - 60
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N07
Revised: July 7, 2020
Table of Contents
Model Nomenclature – General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
TC - Horizontal – Dimensional Data 20
TCH with WSE – Dimensional Data 22
TC - Horizontal Service Access 24
TC - Vertical Upow – Dimensional Data 25
TCV with WSE – Dimensional Data 27
TC - Vertical Service Access 29
Electrical Data – Standard Unit 30
Electrical Data – High Static Blower 31
Electrical Data – Constant Torque ECM 32
Electrical Data – Constant Volume ECM 33
Electrical – Line Voltage 34
Eletctical – Power & Low Voltage Wiring 35
Electrical – Low Voltage Wiring 36
Electrical – Thermostat Wiring 37
Blower Performance Data – TC006 38
Blower Performance Data – TC009 39
Blower Performance Data – TC012 40
Blower Performance Data – TC015 41
Blower Performance Data – TC018 42
Blower Performance Data – TC024 43
Blower Performance Data – TC030 44
Blower Performance Data – TC036 45
Blower Performance Data – TC041 46
Blower Performance Data – TC042 47
Blower Performance Data – TC048 48
Blower Performance Data – TC060 49
Constant Volume ECM Control 50
Wiring Diagram Matrix 52
DIP Setting Table 53
CXM Controls 54
DXM2 Controls 55
Safety Features – CXM and DXM2 Controls 60
Unit Starting and Operating Conditions 62
Piping System Cleaning and Flushing 63
TC with Waterside Economizer Option 64

Table of Contents

Other manuals for ClimateMaster Tranquility 16 Compact Series

Questions and Answers

  • T
    Terry FarmerNov 25, 2025
    What to do if my ClimateMaster Tranquility 16 Compact Heat Pump shows HP Fault Code 2 High Pressure?
    • M
      Michael JamesNov 25, 2025
      If your ClimateMaster Heat Pump displays a High Pressure fault, consider these potential causes and solutions: * **Reduced or no water flow in cooling:** Check pump or valve operation/setting and adjust water flow to the proper rate. Also, ensure the water temperature is within the design parameters. * **Reduced or no air flow in heating:** Inspect and clean or replace the air filter. Check the fan motor operation and airflow for any restrictions. Ensure there is no construction dust on the air coil. Verify the external static pressure against the blower table. Bring the return air temperature within the design parameters. * **Overcharged refrigerant:** Check superheat/subcooling against the typical operating condition table. * **Faulty HP Switch:** Check the switch's continuity a...
  • T
    Todd JonesAug 23, 2025
    Why does only the fan run on my ClimateMaster Tranquility 16 Compact?
    • P
      Patrick GrossAug 25, 2025
      If only the fan is running on your ClimateMaster Heat Pump, consider these possibilities: * **Thermostat position:** Ensure the thermostat is set for heating or cooling operation. * **Unit locked out:** Check for lockout codes and reset power. * **Compressor Overload:** Check the compressor overload and replace it if necessary. * **Thermostat wiring:** Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • W
    William ParksAug 25, 2025
    How to troubleshoot main power problems in ClimateMaster Tranquility 16 Compact?
    • D
      Daniel SanchezAug 26, 2025
      To troubleshoot main power issues, verify the green status LED. If it's off: * Check the line voltage circuit breaker and disconnect. * Check for line voltage between L1 and L2 on the contactor. * Check for 24VAC between R and C on CXM/DXM. * Check the primary/secondary voltage on the transformer.
  • J
    Jessica SwansonAug 27, 2025
    Why is my ClimateMaster Tranquility 16 Compact Heat Pump showing Condensate Fault Code 6?
    • U
      ukingAug 27, 2025
      If your ClimateMaster Heat Pump is showing Condensate Fault Code 6, the following issues might be the cause: * **Blocked drain:** Check for blockage and clean the drain. * **Improper trap:** Check the trap dimensions and location ahead of the vent. * **Poor drainage:** Check for proper piping slope away from the unit and the unit's slope toward the outlet. * **Poor venting:** Check the vent location. * **Moisture on sensor:** Check for moisture shorting to the air coil. * **Plugged air filter:** Replace the air filter. * **Restricted Return Air Flow:** Find and eliminate the restriction. Increase return duct and/or grille size.
  • W
    William WhiteAug 28, 2025
    How do I fix LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) on my ClimateMaster Tranquility 16 Compact Heat Pump?
    • R
      Robert ShepherdAug 28, 2025
      To address a Low Pressure/Loss of Charge fault on your ClimateMaster Heat Pump, check for refrigerant leaks if you suspect insufficient charge. Also, if the compressor pumps down at start-up, verify the charge and start-up water flow.
  • B
    Benjamin WhiteSep 18, 2025
    What causes only the fan to run on my ClimateMaster Tranquility 16 Compact?
    • M
      Mrs. Jennifer Hansen MDSep 18, 2025
      If only the fan is running on your ClimateMaster Heat Pump, ensure the thermostat is set for heating or cooling operation. Check for lockout codes and reset power if necessary. Inspect the compressor overload and replace if needed. Check the thermostat wiring at the heat pump; jumper Y and R for compressor operation in test mode.
  • T
    Tiffany CruzSep 15, 2025
    What does Over/Under Voltage Code 7 mean for my ClimateMaster Tranquility 16 Compact Heat Pump?
    • E
      Ebony BellSep 15, 2025
      If your ClimateMaster Heat Pump is showing Over/Under Voltage Code 7 (Auto resetting), it may be due to under voltage. Check the power supply and 24VAC voltage before and during operation. Also, check the power supply wire size. Check compressor starting and consider if a hard start kit is needed. Verify the 24VAC and unit transformer tap for correct power supply voltage. If it is due to over voltage, check the power supply voltage and 24VAC before and during operation. Also, check the 24VAC and unit transformer tap for correct power supply voltage.
  • A
    Angela WilliamsSep 16, 2025
    Why is my ClimateMaster Tranquility 16 Compact short cycling?
    • S
      smithrachelSep 16, 2025
      If your ClimateMaster Heat Pump is short cycling, it could be due to a dirty air filter; check and clean the air filter. The unit might be in 'test mode'; reset power or wait 20 minutes for auto exit. The unit may be oversized for the space; check the sizing for the actual load of the space. Check the compressor overload and replace if necessary.
  • J
    Justin SandersSep 6, 2025
    What to do if my ClimateMaster Tranquility 16 Compact has no fault code but isn't working properly?
    • R
      Rachael TaylorSep 6, 2025
      If your ClimateMaster Heat Pump isn't showing a fault code but isn't functioning correctly: * **No compressor operation:** Refer to the troubleshooting steps for "Only Fan Operates". * **Compressor overload:** Check the compressor overload and replace if necessary. * **Control board:** Reset power and check operation.
  • A
    Anthony AguilarSep 4, 2025
    What does Unit Performance Sentinel Code 8 mean on my ClimateMaster Tranquility 16 Compact?
    • R
      Ryan BrownSep 4, 2025
      A Unit Performance Sentinel Code 8 on your ClimateMaster Heat Pump indicates a performance issue: * **Heating mode FP2>125°F [52°C]:** Check for poor air flow or an overcharged unit. * **Cooling Mode FP1>125°F [52°C] OR FP2< 40ºF [4ºC]):** Check for poor water flow or air flow.

Summary

Model Nomenclature and Overview

Model Nomenclature Details

Explains the model number structure and component options.

General Information and Safety

Safety Precautions

Covers DANGER, WARNING, CAUTION, and NOTICE statements for safe operation.

Installation Procedures

Pre-Installation and Unit Preparation

Steps before unit installation, including checks and preparation.

Unit Data and Specifications

Physical and Dimensional Data

Specifications for unit physical characteristics and detailed measurements.

Water Quality Standards

Guidelines for evaluating water quality for heat exchangers.

Installation Guidance

Horizontal Installation

Guidelines for installing horizontal units, including location, mounting, and conversion.

Vertical Installation

Guidelines for installing vertical units, including location, mounting, and details.

Piping and Ducting Installation

Requirements for condensate lines, ductwork, and water piping.

Water Source Heat Pump Applications

Application Types

Details on water-loop, ground-loop, and ground-water system applications.

Electrical Systems

Electrical Data

Specifications for standard, high static, and ECM motor configurations.

Electrical Wiring

Guidelines for line voltage, low voltage, and thermostat wiring.

Blower Performance Data

Blower Performance Data

Airflow and static pressure data for various TC models.

Control Systems

Control System Operation and Configuration

Details on ECM control, wiring diagrams, DIP settings, CXM, and DXM2.

Safety Features - Controls

Control Safety Features

Details on anti-short cycle, fault retry, lockout, and pressure protection features.

Unit Operation and Maintenance

Unit Operation and Checkout

Recommended conditions, start-up, and checkout procedures.

Preventive Maintenance

Recommended maintenance tasks for optimal performance and longevity.

Troubleshooting

Troubleshooting Guides

Common faults, performance issues, and cycle analysis with solutions.

Start-Up Log Sheet