Tranquility
®
16
COMPACT (TC) Series
MODELS TCH/V 006 - 60
60 HZ - HFC-410A
INSTALLATION, OPERATION
& MAINTENANCE
97B0075N07
Revised: July 7, 2020
Table of Contents
Model Nomenclature – General Overview 3
General Information 4
Unit Physical Data 6
Horizontal Installation 7
Field Conversion of Air Discharge 9
Horizontal Installation 10
Vertical Installation 11
Piping Installation 13
Water-Loop Heat Pump Applications 14
Ground-Loop Heat Pump Applications 15
Ground-Water Heat Pump Applications 17
Water Quality Standards 19
TC - Horizontal – Dimensional Data 20
TCH with WSE – Dimensional Data 22
TC - Horizontal Service Access 24
TC - Vertical Upow – Dimensional Data 25
TCV with WSE – Dimensional Data 27
TC - Vertical Service Access 29
Electrical Data – Standard Unit 30
Electrical Data – High Static Blower 31
Electrical Data – Constant Torque ECM 32
Electrical Data – Constant Volume ECM 33
Electrical – Line Voltage 34
Eletctical – Power & Low Voltage Wiring 35
Electrical – Low Voltage Wiring 36
Electrical – Thermostat Wiring 37
Blower Performance Data – TC006 38
Blower Performance Data – TC009 39
Blower Performance Data – TC012 40
Blower Performance Data – TC015 41
Blower Performance Data – TC018 42
Blower Performance Data – TC024 43
Blower Performance Data – TC030 44
Blower Performance Data – TC036 45
Blower Performance Data – TC041 46
Blower Performance Data – TC042 47
Blower Performance Data – TC048 48
Blower Performance Data – TC060 49
Constant Volume ECM Control 50
Wiring Diagram Matrix 52
DIP Setting Table 53
CXM Controls 54
DXM2 Controls 55
Safety Features – CXM and DXM2 Controls 60
Unit Starting and Operating Conditions 62
Piping System Cleaning and Flushing 63
TC with Waterside Economizer Option 64

Table of Contents

Other manuals for ClimateMaster Tranquility 16 Compact Series

Questions and Answers

  • P
    pwebbSep 10, 2025
    What causes LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) in a ClimateMaster Tranquility 16 Compact?
    • D
      Dr. Elizabeth GillSep 10, 2025
      If your ClimateMaster Heat Pump shows a Low Pressure/Loss of Charge fault (Code 3), it might be due to insufficient charge. Check for refrigerant leaks. Also, check the charge and start-up water flow.
  • T
    Tom KlineSep 7, 2025
    How to troubleshoot main power problems in my ClimateMaster Tranquility 16 Compact?
    • B
      Brandy RobertsSep 8, 2025
      If the green status LED is off on your ClimateMaster Heat Pump, start by checking the line voltage circuit breaker and disconnect. Also, check for line voltage between L1 and L2 on the contactor. Further, verify that there is 24VAC between R and C on CXM/DXM2. Finally, examine the primary and secondary voltage on the transformer.
  • D
    Donald MartinezAug 22, 2025
    Why does my ClimateMaster Heat Pump short cycle?
    • M
      mkirkAug 22, 2025
      Your ClimateMaster Heat Pump might be short cycling due to: * A dirty air filter: Check and clean the air filter. * The unit being in "test mode": Reset power or wait 20 minutes for auto exit. * Improper unit selection: The unit may be oversized for the space. Check the sizing for the actual load of the space. * Compressor overload: Check and replace the compressor if necessary.
  • S
    Sandra GomezSep 5, 2025
    Why does only the compressor run on my ClimateMaster Heat Pump?
    • C
      Cody RyanSep 5, 2025
      If only the compressor runs on your ClimateMaster Heat Pump, check the following: * **Thermostat wiring:** Check the G wiring at the heat pump. Jumper G and R for fan operation. * **Fan motor relay:** Jumper G and R for fan operation. Check for Line voltage across BR contacts. * **Fan power enable relay:** Check fan power enable relay operation (if present). * **Fan motor:** Check for line voltage at the motor and check the capacitor. * **Thermostat wiring:** Check the thermostat wiring at the heat pump. Jumper Y and R for compressor operation in test mode.
  • A
    Anthony AguilarSep 4, 2025
    What does Unit Performance Sentinel Code 8 mean on my ClimateMaster Tranquility 16 Compact?
    • R
      Ryan BrownSep 4, 2025
      A Unit Performance Sentinel Code 8 on your ClimateMaster Heat Pump indicates a performance issue: * **Heating mode FP2>125°F [52°C]:** Check for poor air flow or an overcharged unit. * **Cooling Mode FP1>125°F [52°C] OR FP2< 40ºF [4ºC]):** Check for poor water flow or air flow.
  • S
    Sandra PaceSep 2, 2025
    What does LT2 Fault Code 5 (Air coil low temperature limit) mean for my ClimateMaster Heat Pump?
    • J
      jmckeeSep 2, 2025
      LT2 Fault Code 5 indicates a low temperature limit on the air coil. This can be caused by: * **Reduced or no air flow in cooling:** Check for a dirty air filter and clean or replace it. Also, check the fan motor operation and airflow restrictions. Ensure the external static is not too high by checking the static vs. blower table. * **Air Temperature out of range:** Ensure the entering air temperature is within design parameters. * **Improper temperature limit setting:** Normal airside applications typically require 30°F [-1°C] only. * **Bad thermistor:** Check the temperature and impedance correlation per the chart.
  • G
    gilberttheresaSep 1, 2025
    What causes Over/Under Voltage Code 7 on ClimateMaster Tranquility 16 Compact?
    • O
      ocollinsSep 1, 2025
      An Over/Under Voltage Code 7 on your ClimateMaster Heat Pump can stem from several power-related issues: * **Under Voltage:** Check the power supply and 24VAC voltage, both before and during operation. Also, check the power supply wire size, compressor starting (consider a hard start kit), and the 24VAC and unit transformer tap for correct power supply voltage. * **Over Voltage:** Check the power supply voltage and 24VAC, both before and during operation. Also, check the 24VAC and unit transformer tap for correct power supply voltage.
  • T
    Theresa CoxAug 31, 2025
    What causes LT1 Fault Code 4 (Water coil low temperature limit) in ClimateMaster Tranquility 16 Compact Heat Pump and how to resolve it?
    • K
      kim03Aug 31, 2025
      The LT1 Fault Code 4 indicates a low temperature limit on the water coil. Possible causes include: * **Reduced or no water flow in heating:** Check the pump or water valve operation/setting. Also, check for plugged strainers or filters and clean or replace them. Ensure the water flow is adjusted to the proper rate. * **Inadequate antifreeze level:** Check the antifreeze density with a hydrometer. * **Improper temperature limit setting:** Clip the JW3 jumper for antifreeze (10°F [-12°C]) use. * **Water Temperature out of range:** Bring water temperature within design parameters. * **Bad thermistor:** Check the temperature and impedance correlation per the chart.
  • A
    Ashley StewartAug 30, 2025
    What should I do if my ClimateMaster Heat Pump doesn’t operate in cooling mode?
    • T
      Terry MclaughlinAug 30, 2025
      If your ClimateMaster Heat Pump isn't cooling, here's what you can check: * **Reversing valve:** Ensure it's set for cooling and check for 24VAC on the RV coil and at the CXM/DXM board. If the valve is stuck, try running high pressure by reducing water flow while engaging and disengaging the RV coil voltage to try to move the valve. * **Thermostat setup:** Verify the thermostat is set to 'O' for the reversing valve, not 'B'. * **Thermostat wiring:** Check the O wiring at the heat pump by jumpering O and R to listen for an RV coil 'click'. Also, put the thermostat in cooling mode and check for 24 VAC on O (between C and O) and W (between W and C). Voltage should be present on O, but not on W. If there's voltage on W, the thermostat may be faulty or incorrectly wired.
  • W
    William WhiteAug 28, 2025
    How do I fix LP/LOC Fault Code 3 (Low Pressure / Loss of Charge) on my ClimateMaster Tranquility 16 Compact Heat Pump?
    • R
      Robert ShepherdAug 28, 2025
      To address a Low Pressure/Loss of Charge fault on your ClimateMaster Heat Pump, check for refrigerant leaks if you suspect insufficient charge. Also, if the compressor pumps down at start-up, verify the charge and start-up water flow.

Summary

Model Nomenclature and Overview

Model Nomenclature Details

Explains the model number structure and component options.

General Information and Safety

Safety Precautions

Covers DANGER, WARNING, CAUTION, and NOTICE statements for safe operation.

Installation Procedures

Pre-Installation and Unit Preparation

Steps before unit installation, including checks and preparation.

Unit Data and Specifications

Physical and Dimensional Data

Specifications for unit physical characteristics and detailed measurements.

Water Quality Standards

Guidelines for evaluating water quality for heat exchangers.

Installation Guidance

Horizontal Installation

Guidelines for installing horizontal units, including location, mounting, and conversion.

Vertical Installation

Guidelines for installing vertical units, including location, mounting, and details.

Piping and Ducting Installation

Requirements for condensate lines, ductwork, and water piping.

Water Source Heat Pump Applications

Application Types

Details on water-loop, ground-loop, and ground-water system applications.

Electrical Systems

Electrical Data

Specifications for standard, high static, and ECM motor configurations.

Electrical Wiring

Guidelines for line voltage, low voltage, and thermostat wiring.

Blower Performance Data

Blower Performance Data

Airflow and static pressure data for various TC models.

Control Systems

Control System Operation and Configuration

Details on ECM control, wiring diagrams, DIP settings, CXM, and DXM2.

Safety Features - Controls

Control Safety Features

Details on anti-short cycle, fault retry, lockout, and pressure protection features.

Unit Operation and Maintenance

Unit Operation and Checkout

Recommended conditions, start-up, and checkout procedures.

Preventive Maintenance

Recommended maintenance tasks for optimal performance and longevity.

Troubleshooting

Troubleshooting Guides

Common faults, performance issues, and cycle analysis with solutions.

Start-Up Log Sheet

Warranty Information

Warranty Terms

Limited express warranty terms for U.S., Canada, and international.

Revision History

ClimateMaster Tranquility 16 Compact Series Specifications

General IconGeneral
BrandClimateMaster
ModelTranquility 16 Compact Series
CategoryHeat Pump
LanguageEnglish

Related product manuals