TERMINAL EVOLUTION
USER DEFAULT VALUES
AIU
Set points and differential band
Cooling set point °C 24 17 35
Cooling proportional band °C 1.5 0.5 9.9
Heating set point °C 24 12 30
Heating proportional band °C 1.5 0.5 9.9
Dehumidification set point % 55 45 90
Dehumidification proportional band % 5 3 15
Humidification set point % 45 10 55
Humidification proportional band % 5 3 15
Maintenance operating hour threshold
Fan h 00000 00000 32767
Compressor 1 h 00000 00000 32767
Compressor 2 h 00000 00000 32767
Heaters 1 h 00000 00000 32767
Heaters 2 h 00000 00000 32767
Humidifier h 00000 00000 32767
Alarm parameters
High ambient temperature threshold °C 32 20 50
Low ambient temperature threshold °C 10 0 30
High ambient humidity threshold % 80 30 99
Low ambient humidity threshold % 30 0 70
High water temperature threshold °C 15 5 50
High water temperature threshold in dehumidification °C 7 0 30
Flow alarm delay after unit start-up s 15 15 999
Alarm delays when exceeding temperature and humidity limits s 60 0 999
Blocked filter alarm delay s 8 2 999
Low pressure alarm delay after compressor start s 180 2 999
Reset temperature limit alarm Auto MAN Auto
Reset humidity limit alarm Auto MAN Auto
Reset high water temperature alarm Auto MAN Auto
Reset low pressure alarm Auto MAN Auto
Reset humidifier Alarm Auto MAN Auto
Reset water flow alarm Auto MAN Auto
Select alarm output A
LAN parameters
High temperature threshold to switch the unit on in standby °C 30 20 50
Low temperature threshold to switch the unit on in standby °C 18 0 30
High humidity threshold to switch the unit on in standby % 75 55 90
Low humidity threshold to switch the unit on in standby % 35 10 45
Serial parameters
Serial address 1
Serial baud rate baud 1200
Protocol Standard
Advanced control parameters
Unit start delay s 0 0 999
Control start delay after unit start-up s 60 20 999
Integration time s 900 0 999
Enable minimum outlet air temperature limit Y
Minimum outlet temperature limit set point °C 12 0 25
Enable dehumidification function Y
Hot water activation set point °C 40 20 99.9
U.M. DEFAULT MIN MAX