EasyManua.ls Logo

CLIVET ELFOFresh2 CPAN-U 70-120 Series - Electrical data; F.L.A. - Full load current at max admissible conditions; F.L.I. - Full load power input at max admissible conditions; Electrical input of optional components

CLIVET ELFOFresh2 CPAN-U 70-120 Series
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24 ELFOFresh² BT15B012GB-00
Electrical data
Size 70 120 200 300 500 650
F.L.A. - Full load current at max admissible conditions
F.L.A. - Compressor 1 A 0,87 1,62 2.20 3.10 5.13 6.80
F.L.A. - Single supply fan A 0,30 0,90 1.20 1.20 1.20 1.20
F.L.A. - Single exhaust air fan A 0,30 0,90 1.20 1.20 1.20 1.20
F.L.A. - Total A 1,47 3,42 5.60 6.50 8.53 10.2
L.R.A. - Locked rotor amperes
L.R.A. - Compressor 1 A 4,35 8,10 12.0 16.5 25.2 37.0
F.L.I. - Full load power input at max admissible conditions
F.L.I. - Compressor 1 kW 0,19 0,34 0.47 0.69 1.10 1.52
F.L.I. - Single External Fan kW 0,037 0,115 0.165 0.165 0.165 0.165
F.L.I. – Single exhaust air fan kW 0,037 0,115 0.165 0.165 0.165 0.165
F.L.I. - Total kW 0,264 0,57 1.03 1.25 1.66 2.08
M.I.C. Maximum inrush current
M.I.C. - Value A 4,95 9,9 14.4 18.9 23.4 39.4
power supply 230/1/50 Hz +/-10%
Electrical input of optional components
To obtain the electrical input of the unit including accessories, add the standard data in Electrical Data table to those for the selected accessories.
Size 70 120 200 300 500 650
F.L.A. - Full load current at max admissible conditions
F.L.A. EHPCX - Preheating electric heaters from 0.7 kW A 3,04 3,04 - - - -
F.L.A. EHPCX - Preheating electric heaters from 1.5 kW A - - 6,5 6,5 - -
F.L.A. EHPCX - Preheating electric heaters from 3 kW A - - - - 13 13
F.L.A. HSE3MX/HSE3LX - Electrode boiler steam humidier from 3 kg/h A - - 9,8 9,8 9,8 9,8
F.L.A. FES/FESX - Electronic lter A 0,1 0,1 0,1 0,1 0,1 0,1
F.L.A. CDP - Condensate discharge pump A 0,07 0,07 0,07 0,07 0,07 0,07
F.L.I. Power consumption
F.L.I. EHPCX - Preheating electric heaters from 0.7 kW kW 0,7 0,7 - - - -
F.L.I. EHPCX - Preheating electric heaters from 1.5 kW kW - - 1,5 1,5 - -
F.L.I. EHPCX - Preheating electric heaters from 3 kW kW - - - - 3 3
F.L.I. HSE3MX/HSE3LX - Electrode boiler steam humidier from 3 kg/h kW - - 2,25 2,25 2,25 2,25
F.L.I. FES/FESX - Electronic lter kW 0,025 0,025 0,025 0,025 0,025 0,025
F.L.I. CDP - Condensate discharge pump kW 0,016 0,016 0,016 0,016 0,016 0,016

Table of Contents

Related product manuals