24 ELFOFresh² BT15B012GB-00
Electrical data
Size 70 120 200 300 500 650
F.L.A. - Full load current at max admissible conditions
F.L.A. - Compressor 1 A 0,87 1,62 2.20 3.10 5.13 6.80
F.L.A. - Single supply fan A 0,30 0,90 1.20 1.20 1.20 1.20
F.L.A. - Single exhaust air fan A 0,30 0,90 1.20 1.20 1.20 1.20
F.L.A. - Total A 1,47 3,42 5.60 6.50 8.53 10.2
L.R.A. - Locked rotor amperes
L.R.A. - Compressor 1 A 4,35 8,10 12.0 16.5 25.2 37.0
F.L.I. - Full load power input at max admissible conditions
F.L.I. - Compressor 1 kW 0,19 0,34 0.47 0.69 1.10 1.52
F.L.I. - Single External Fan kW 0,037 0,115 0.165 0.165 0.165 0.165
F.L.I. – Single exhaust air fan kW 0,037 0,115 0.165 0.165 0.165 0.165
F.L.I. - Total kW 0,264 0,57 1.03 1.25 1.66 2.08
M.I.C. Maximum inrush current
M.I.C. - Value A 4,95 9,9 14.4 18.9 23.4 39.4
power supply 230/1/50 Hz +/-10%
Electrical input of optional components
To obtain the electrical input of the unit including accessories, add the standard data in Electrical Data table to those for the selected accessories.
Size 70 120 200 300 500 650
F.L.A. - Full load current at max admissible conditions
F.L.A. EHPCX - Preheating electric heaters from 0.7 kW A 3,04 3,04 - - - -
F.L.A. EHPCX - Preheating electric heaters from 1.5 kW A - - 6,5 6,5 - -
F.L.A. EHPCX - Preheating electric heaters from 3 kW A - - - - 13 13
F.L.A. HSE3MX/HSE3LX - Electrode boiler steam humidier from 3 kg/h A - - 9,8 9,8 9,8 9,8
F.L.A. FES/FESX - Electronic lter A 0,1 0,1 0,1 0,1 0,1 0,1
F.L.A. CDP - Condensate discharge pump A 0,07 0,07 0,07 0,07 0,07 0,07
F.L.I. Power consumption
F.L.I. EHPCX - Preheating electric heaters from 0.7 kW kW 0,7 0,7 - - - -
F.L.I. EHPCX - Preheating electric heaters from 1.5 kW kW - - 1,5 1,5 - -
F.L.I. EHPCX - Preheating electric heaters from 3 kW kW - - - - 3 3
F.L.I. HSE3MX/HSE3LX - Electrode boiler steam humidier from 3 kg/h kW - - 2,25 2,25 2,25 2,25
F.L.I. FES/FESX - Electronic lter kW 0,025 0,025 0,025 0,025 0,025 0,025
F.L.I. CDP - Condensate discharge pump kW 0,016 0,016 0,016 0,016 0,016 0,016