38 ELFOFresh² BT15B012GB-00
HSE3LX: Immersed electrode humidier DN200 (size 200-300)
HSE3MX: Immersed electrode humidier DN250 (size 500-650)
For the ambient air humidifcation it is possible to mount in the outlet duct a humidier with steam distributor. The regulation of steam production, realized
from the electronic of Elfofresh2 unit, can be modulated according to setpoint and relative humidity from the ambient thermostat probe (necessary in
presence of humidier). The humidifer is equipped with power supply and water inlet/outlet and it needs only the replacemnet of the cylinder boiler when
the limestone deposits exceed the available limits.
steam distribution
(AE) fresh air inlet
(ES) Exhaust air
(M)Ambient air supply
(R) Ambient air return
steam production
In the event of limited space, the steam production module can be separated from the steam
distribution module and installed in another position, for example, wall-mounted, up to 4
meters away. The steam tube rising segment must maintain a gradient no lower than 20°.
CMMBX - Serial communication module to supervisor (MODBUS)
This enables the serial connection of the supervision system and to the ELFOControl2, using Modbus as the communication protocol.
It enables access to the complete list of operational variables, commands and alarms.
Using this accessory every unit can dialogue with the main supervision systems.