If the following conditions are satisfied, the
compressor ceases operation.
While calculated frequency(fb) is less than minimum
limit frequency(FminC).
While protective time is more than or equal to ten
minutes.
While T1 is lower than or equal to (Tsc-CDIFTEMP-
0.5°C)
2) When the compressor runs continuously for more than
120 minutes.
If the following conditions are satisfied, the
compressor ceases operation.
When calculated frequency(fb) is less than minimum
limit frequency(FminC).
When protective time is more than or equal to ten
minutes.
When T1 is lower than or equal to (Tsc-CDIFTEMP).
3) If one of the following conditions is satisfied, not judge
protective time.
Compressor running frequency is more than test
frequency.
When compressor running frequency is equal to
test frequency, T4 is more than 15°C or T4 fault.
Change setting temperature.
Turbo or sleep function on/off
Various frequency limit shutdown occurs.
1.5.2 Indoor Fan Control
1) In cooling mode, the indoor fan operates continuously.
The fan speed can be set to 1%-100%, or low,
medium, high and auto.
2) Auto fan action in cooling mode:
Descent curve
When T1-Tsc is lower than or equal to 3.5°C, fan
speed reduces to 80%;
-When T1-Tsc is lower than or equal to 1°C, fan
speed reduces to 60%;
-When T1-Tsc is lower than or equal to 0.5°C, fan
speed reduces to 40%;
-When T1-Tsc is lower than or equal to 0°C, fan
speed reduces to 20%;
-When T1-Tsc is lower than or equal to -0.5°C, fan
speed reduces to 1%.
Rise curve
When T1-Tsc is higher than 0°C, fan speed
increases to 20%;
-When T1-Tsc is higher than 0.5°C, fan speed
increases to 40%;
-When T1-Tsc is higher than 1°C, fan speed
increases to 60%;
-When T1-Tsc is higher than 1.5°C, fan speed
increases to 80%;
-When T1-Tsc is higher than 4°C, fan speed
increases to 100%.
1.5.3 Outdoor Fan Control
The outdoor unit will be run at different fan speed
according to T4 and compressor frequency.
For different outdoor units, the fan speeds are
different.
1.5.4 Condenser Temperature Protection
When the condenser temperature exceeds a configured
value, the compressor ceases operation.
1.5.5 Evaporator Temperature Protection
Off: Compressor stops.
Decrease: Decrease the running frequency to the lower
level per 1 minute.
Hold: Keep the current frequency.
Resume: No limitation for frequency.
1.6 Heating Mode(Heat Pump Units)
1.6.1 Compressor Control